Transformer Full Load Amps Chart: Complete FLA Reference

Quick reference tables for transformer full load current at all standard voltages, plus formulas and wire sizing
recommendations

Full Load Amps Formulas

Single-Phase:
FLA = (kVA × 1000) ÷ Voltage
Three-Phase:
FLA = (kVA × 1000) ÷ (V × 1.732)

The full load amps (FLA) of a transformer is the maximum current the transformer can deliver at its
rated kVA and voltage without exceeding its thermal limits. This chart provides quick reference values for sizing
conductors, overcurrent protection, and system design.


Table of Contents


Single-Phase Transformer Full Load Amps Chart

Full load current for single-phase transformers at standard voltages:

kVA120V208V240V277V480V600V
325.014.412.510.86.25.0
541.724.020.818.110.48.3
7.562.536.131.227.115.612.5
1083.348.141.736.120.816.7
15125.072.162.554.231.225.0
25208.3120.2104.290.352.141.7
37.5312.5180.3156.2135.478.162.5
50416.7240.4208.3180.5104.283.3
75625.0360.6312.5270.8156.2125.0
100833.3480.8416.7361.0208.3166.7
1671391.7803.0695.8602.9347.9278.3
2502083.31201.91041.7902.5520.8416.7
3332775.01600.91387.51202.2693.8555.0
5004166.72403.82083.31805.11041.7833.3
📝 Note: Values calculated using formula: FLA = (kVA × 1000) ÷ Voltage. For detailed specifications
of each size, see our Transformer
Sizing Chart
.

Three-Phase Transformer Full Load Amps Chart

Full load current for three-phase transformers at standard voltages:

kVA208V240V380V480V600V
925.021.613.710.88.7
1541.636.122.818.014.4
3083.372.245.636.128.9
45124.9108.368.454.143.3
75208.2180.4114.090.272.2
112.5312.3270.6171.0135.3108.2
150416.4360.8228.0180.4144.3
225624.6541.3342.0270.6216.5
300832.8721.7456.0360.8288.7
5001388.01202.8760.0601.4481.1
7502082.01804.21140.0902.1721.7
10002776.02405.61520.01202.8962.3
15004164.03608.42280.01804.21443.4
20005552.04811.33040.02405.61924.5
25006940.06014.13800.03007.02405.6
Formula Used:
FLA = (kVA × 1000) ÷ (Voltage × 1.732)
where 1.732 = √3 (the square root of 3 for three-phase calculations)

Wire Sizing Guide Based on FLA

Recommended minimum wire sizes based on full load amps (copper conductors, 75°C rating per NEC):

Full Load AmpsMinimum Wire Size (AWG/MCM)Recommended Conduit Size
0-15 A#14 AWG1/2″
16-20 A#12 AWG1/2″
21-30 A#10 AWG1/2″
31-40 A#8 AWG3/4″
41-55 A#6 AWG3/4″
56-70 A#4 AWG1″
71-85 A#3 AWG1″
86-100 A#2 AWG1-1/4″
101-115 A#1 AWG1-1/4″
116-130 A1/0 AWG1-1/2″
131-150 A2/0 AWG1-1/2″
151-175 A3/0 AWG2″
176-200 A4/0 AWG2″
201-230 A250 MCM2-1/2″
231-255 A300 MCM2-1/2″
256-285 A350 MCM3″
286-310 A400 MCM3″
311-380 A500 MCM3-1/2″

Calculation Examples

Example 1: Single-Phase 25 kVA at 480V

Given: 25 kVA single-phase transformer, 480V secondary

Formula: FLA = (kVA × 1000) ÷ Voltage

Calculation: FLA = (25 × 1000) ÷ 480 = 52.1 amps

Wire Size: #6 AWG (rated for 55A)

Example 2: Three-Phase 500 kVA at 480V

Given: 500 kVA three-phase transformer, 480V secondary

Formula: FLA = (kVA × 1000) ÷ (Voltage × 1.732)

Calculation: FLA = (500 × 1000) ÷ (480 × 1.732) = 601.4 amps

Wire Size: Parallel 350 MCM or 500 MCM conductors


Frequently Asked Questions

What is full load amps (FLA) on a transformer?

Full load amps is the maximum current the transformer can continuously deliver at its rated kVA and voltage without
overheating. It’s used for sizing conductors and overcurrent protection.

Why do three-phase transformers have lower FLA than single-phase at the same kVA?

Three-phase power is distributed across three conductors, so each conductor carries less current. The formula
includes the √3 factor to account for this distribution.

How do I calculate FLA for a voltage not shown in the chart?

Use the formulas:
Single-phase: FLA = (kVA × 1000) ÷ Voltage
Three-phase: FLA = (kVA × 1000) ÷ (Voltage × 1.732)

What overcurrent protection should I use?

Per NEC 450.3, transformer primary overcurrent protection should be 125% of rated primary current for transformers 9
kVA and larger. Consult local codes for specific requirements.


Related Resources


Disclaimer: Values calculated using standard electrical formulas. Wire sizing based on NEC Table 310.16 for 75°C
copper conductors. Always consult a licensed electrician and verify with local codes. Last updated: January
2026

Scroll to Top