Comprehensive transformer sizing reference with kVA ratings, full load amps, dimensions, and selection guidelines
for electrical engineers and contractors
Quick Sizing Formula
Single-Phase:kVA = (Volts × Amps) ÷ 1000 | Three-Phase:kVA = (Volts × Amps × 1.732) ÷ 1000 |
Selecting the right transformer size is critical for electrical system reliability and efficiency. This comprehensive
transformer sizing chart provides all the data you need to choose the correct kVA rating for your
application.
expansion and prevent overloading. Never load a transformer above 80% of its rated capacity for continuous
operation.
Table of Contents
- Single-Phase Transformer Sizing Chart
- Three-Phase Transformer Sizing Chart
- Full Load Amps Reference Table
- How to Size a Transformer
- Standard kVA Ratings
- FAQ
Single-Phase Transformer Sizing Chart
Standard single-phase transformer ratings with typical dimensions, weights, and efficiency:
| kVA | Dimensions (H×W×D) | Weight | FLA @ 480V | FLA @ 240V | Efficiency | Specifications |
|---|---|---|---|---|---|---|
| 5 kVA | 22″×15″×10″ | 80 lbs | 10.4 A | 20.8 A | 97.8% | View Details → |
| 7.5 kVA | 24″×16″×11″ | 100 lbs | 15.6 A | 31.2 A | 97.9% | View Details → |
| 10 kVA | 26″×16″×12″ | 120 lbs | 20.8 A | 41.7 A | 98.0% | View Details → |
| 15 kVA | 30″×17″×13″ | 170 lbs | 31.2 A | 62.5 A | 98.2% | View Details → |
| 25 kVA | 37″×20″×16″ | 285 lbs | 52.1 A | 104.2 A | 98.5% | View Details → |
| 37.5 kVA | 40″×22″×17″ | 350 lbs | 78.1 A | 156.2 A | 98.6% | View Details → |
| 50 kVA | 43″×24″×18″ | 400 lbs | 104.2 A | 208.3 A | 98.7% | View Details → |
| 75 kVA | 46″×26″×20″ | 500 lbs | 156.2 A | 312.5 A | 98.8% | View Details → |
| 100 kVA | 50″×28″×22″ | 650 lbs | 208.3 A | 416.7 A | 98.9% | View Details → |
| 167 kVA | 55″×30″×24″ | 860 lbs | 347.9 A | 695.8 A | 99.0% | View Details → |
| 250 kVA | 60″×34″×28″ | 1200 lbs | 520.8 A | 1041.7 A | 99.1% | View Details → |
Three-Phase Transformer Sizing Chart
Standard three-phase transformer ratings with typical dimensions, weights, and efficiency:
| kVA | Dimensions (H×W×D) | Weight | FLA @ 480V | FLA @ 208V | Efficiency | Specifications |
|---|---|---|---|---|---|---|
| 15 kVA | 30″×18″×14″ | 190 lbs | 18.0 A | 41.6 A | 98.0% | View Details → |
| 30 kVA | 35″×20″×16″ | 280 lbs | 36.1 A | 83.3 A | 98.3% | View Details → |
| 45 kVA | 38″×22″×17″ | 360 lbs | 54.1 A | 124.9 A | 98.5% | View Details → |
| 75 kVA | 43″×24″×20″ | 500 lbs | 90.2 A | 208.2 A | 98.7% | View Details → |
| 112.5 kVA | 47″×26″×22″ | 650 lbs | 135.3 A | 312.3 A | 98.8% | View Details → |
| 150 kVA | 50″×28″×24″ | 800 lbs | 180.4 A | 416.4 A | 98.9% | View Details → |
| 225 kVA | 55″×30″×26″ | 1050 lbs | 270.6 A | 624.6 A | 99.0% | View Details → |
| 300 kVA | 58″×32″×28″ | 1300 lbs | 360.8 A | 832.8 A | 99.0% | View Details → |
| 500 kVA | 64″×36″×32″ | 1900 lbs | 601.4 A | 1388.0 A | 99.1% | View Details → |
| 750 kVA | 70″×40″×35″ | 2500 lbs | 902.1 A | 2082.0 A | 99.2% | View Details → |
| 1000 kVA | 76″×44″×38″ | 3200 lbs | 1202.8 A | 2776.0 A | 99.2% | View Details → |
| 1500 kVA | 84″×48″×42″ | 4500 lbs | 1804.2 A | 4164.0 A | 99.3% | View Details → |
| 2000 kVA | 90″×52″×46″ | 6000 lbs | 2405.6 A | 5552.0 A | 99.3% | View Details → |
| 2500 kVA | 96″×56″×50″ | 7500 lbs | 3007.0 A | 6940.0 A | 99.4% | View Details → |
Full Load Amps Reference Table
Quick reference for transformer full load amps at common voltages:
Single-Phase Full Load Amps
| kVA | 120V | 208V | 240V | 277V | 480V | 600V |
|---|---|---|---|---|---|---|
| 5 | 41.7 | 24.0 | 20.8 | 18.1 | 10.4 | 8.3 |
| 10 | 83.3 | 48.1 | 41.7 | 36.1 | 20.8 | 16.7 |
| 15 | 125.0 | 72.1 | 62.5 | 54.2 | 31.2 | 25.0 |
| 25 | 208.3 | 120.2 | 104.2 | 90.3 | 52.1 | 41.7 |
| 37.5 | 312.5 | 180.3 | 156.2 | 135.4 | 78.1 | 62.5 |
| 50 | 416.7 | 240.4 | 208.3 | 180.5 | 104.2 | 83.3 |
| 75 | 625.0 | 360.6 | 312.5 | 270.8 | 156.2 | 125.0 |
| 100 | 833.3 | 480.8 | 416.7 | 361.0 | 208.3 | 166.7 |
Three-Phase Full Load Amps
| kVA | 208V | 240V | 480V | 600V |
|---|---|---|---|---|
| 15 | 41.6 | 36.1 | 18.0 | 14.4 |
| 30 | 83.3 | 72.2 | 36.1 | 28.9 |
| 45 | 124.9 | 108.3 | 54.1 | 43.3 |
| 75 | 208.2 | 180.4 | 90.2 | 72.2 |
| 112.5 | 312.3 | 270.6 | 135.3 | 108.2 |
| 150 | 416.4 | 360.8 | 180.4 | 144.3 |
| 225 | 624.6 | 541.3 | 270.6 | 216.5 |
| 300 | 832.8 | 721.7 | 360.8 | 288.7 |
| 500 | 1388.0 | 1202.8 | 601.4 | 481.1 |
| 750 | 2082.0 | 1804.2 | 902.1 | 721.7 |
| 1000 | 2776.0 | 2405.6 | 1202.8 | 962.3 |
How to Size a Transformer
Step 1: Calculate Total Load
Add up the power requirements of all equipment:
- List all loads (motors, lighting, HVAC, etc.)
- Convert horsepower to kVA: HP × 0.746 ÷ PF ÷ Efficiency ≈ kVA
- Account for power factor (typical 0.8-0.9)
Step 2: Apply Safety Factor
Add 25% safety margin for:
- Future expansion
- Motor starting currents
- Harmonics
Total connected load: 18 kVA
Safety factor: × 1.25
Required capacity: 22.5 kVA
Answer: Select 25 kVA transformer
Step 3: Select Standard Size
Choose the next standard size above your calculated requirement:
| Single-Phase Standard Sizes | Three-Phase Standard Sizes |
|---|---|
| 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333 kVA | 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500 kVA |
Standard kVA Ratings (IEEE/ANSI)
| Category | Standard Sizes (kVA) | Typical Application |
|---|---|---|
| Small (Residential) | 5, 7.5, 10, 15 | Homes, small offices |
| Medium (Commercial) | 25, 37.5, 50, 75, 100 | Retail, restaurants, small factories |
| Large (Industrial) | 150, 225, 300, 500 | Manufacturing, warehouses |
| Extra Large (Utility) | 750, 1000, 1500, 2000, 2500 | Substations, heavy industry |
Frequently Asked Questions
What size transformer do I need for 100 amps at 480V?
For a single-phase load: kVA = (480 × 100) ÷ 1000 = 48 kVA. Select a 50 kVA transformer.
For a three-phase load: kVA = (480 × 100 × 1.732) ÷ 1000 = 83.1 kVA. Select a 112.5 kVA
transformer.
What is the full load current of a 75 kVA transformer at 480V?
Single-phase: 75,000 ÷ 480 = 156.2 amps
Three-phase: 75,000 ÷ (480 × 1.732) = 90.2 amps
Can I overload a transformer temporarily?
Most transformers can handle 150% overload for short periods (minutes to hours), but this reduces transformer life.
Avoid sustained overloading above 100%.
Why are transformers rated in kVA instead of kW?
kVA (apparent power) accounts for both real power and reactive power. Since transformers must handle both, they’re
rated in kVA regardless of load power factor.
Related Resources
- Three
Phase Transformer: Complete Guide - Transformer Testing: Complete Guide
- Transformer
Protection: Complete Guide - Transformer Oil:
Complete Guide
Disclaimer: Data shown are typical reference values. Actual specifications vary by manufacturer. Always verify
with manufacturer datasheets before ordering or installation. Full load amps calculated using standard
electrical formulas. Last updated: January 2026