15 kVA Three-Phase Oil-Filled Transformer: Complete Specifications

Comprehensive specifications for 15 kVA ONAN oil-filled transformer including dimensions, weight, oil volume, and electrical data

Quick Specifications

Rated Power:15 kVAPhase:Three-Phase
Primary Voltage:12470Y/7200VSecondary Voltage:208Y/120V
Cooling Class:ONANBIL Rating:95 kV
Weight:500 lbs (227 kg)Oil Volume:20 gallons (76 L)
Dimensions (H×W×D):34″ × 24″ × 18″ (860 × 620 × 460 mm)

A 15 kVA oil-filled transformer is commonly used for Small three-phase loads. This guide provides complete specifications for utility engineers, electrical contractors, and procurement professionals.

⚠️ Important: Oil-filled transformers contain flammable insulating oil. Installation must comply with NEC Article 450, NFPA 70, and local fire codes. Oil containment per EPA SPCC regulations is mandatory.

15 kVA Oil-Filled Transformer Dimensions

15-0-kva-three-phase-oil-filled-transformer-dimensions
15 kVA Three-Phase Oil-Filled Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)860 mm34″
Width (W)620 mm24″
Depth (D)460 mm18″
🔧 Installation Note: This 15 kVA oil-filled transformer weighs 500 lbs and contains 20 gallons of insulating oil. Required:

  • Concrete pad rated for 750 lbs minimum
  • Oil containment per EPA SPCC requirements (110% capacity)
  • Minimum 10ft clearance from buildings for outdoor installation
  • 4-8 hour settling time before energizing

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)500 lbs (227 kg)Includes all oil and accessories
Oil Volume20 gallons (76 L)Mineral Oil
Oil TypeMineral OilIEEE C57.106 compliant
Containment Required22 gallons110% per EPA SPCC

Electrical Specifications

ParameterValueNotes
Rated kVA15 kVAAt rated voltage and ONAN cooling
Primary Voltage12470Y/7200VStandard utility distribution voltage
Secondary Voltage208Y/120VService voltage
Cooling ClassONANOil Natural, Air Natural
BIL Rating95 kVStandard for 12.47kV-15kV primary
No-Load Loss70 WCore losses
Load Loss250 WAt rated load
Total Losses320 WAt 100% load
Impedance3.5%Per IEEE C57.12.00
Efficiency98.0%At rated load
Sound Level~45 dBPer NEMA TR-1

Secondary Full Load Amps

Full load amperage at secondary voltage for 15 kVA three-phase transformer:

Secondary VoltageFull Load AmpsConductor Size
120V72.2 A#3 AWG
208V41.6 A#6 AWG
240V36.1 A#8 AWG
277V31.3 A#8 AWG
480V18.0 A#12 AWG
Formula:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 18.0 A = (15 × 1000) ÷ (480 × 1.732)

Oil Maintenance Guidelines for 15 kVA Transformer

Proper maintenance of the 20 gallons of Mineral Oil in this transformer is critical for long-term reliability:

Maintenance TaskFrequencyPurpose
Visual Oil Level CheckMonthlyDetect leaks, ensure adequate level
Oil Sample AnalysisAnnuallyDielectric strength, dissolved gas analysis (DGA)
Oil Filtration/ReconditioningEvery 3-5 yearsRemove moisture and contaminants
Silica Gel Breather CheckQuarterlyEnsure moisture protection
Bushing InspectionAnnuallyCheck for cracks, contamination, oil leaks
⚠️ Oil Handling Safety:

  • Always use proper PPE when handling transformer oil
  • Dispose of contaminated oil according to EPA regulations
  • Never mix different oil types without compatibility testing
  • Maintain SPCC containment at all times

When to Choose a 15 kVA Three-Phase Oil-Filled Transformer

A 15 kVA three-phase oil-filled transformer is well-suited for:

  • Commercial building service entrance
  • Small manufacturing facilities
  • Utility distribution substations
  • Shopping centers and retail developments
  • Medium-voltage industrial applications

Cooling Class ONAN: 自然油循环、自然空气冷却

Typical Load Distribution for 15 kVA Oil-Filled Transformer

Example utility distribution loads for a 15 kVA oil-filled transformer:

Load TypeEstimated Demand
Three-phase motor loads6 kVA
HVAC systems3 kVA
Lighting transformers2 kVA
Receptacle/misc loads3 kVA

Note: Utility distribution varies by application. Consult with utility engineer for specific load allocations.


Related Oil-Filled Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
15 kVA Three-Phase15 kVA Oil-Filled Specs →
15 kVA Three-PhaseCurrent Page
30 kVA Three-Phase30 kVA Oil-Filled Specs →

Frequently Asked Questions

How much oil does a 15 kVA oil-filled transformer contain?

A 15 kVA three-phase oil-filled transformer typically contains 20 gallons (76 liters) of Mineral Oil insulating oil.

What are the dimensions of a 15 kVA oil-filled transformer?

Typical dimensions are 34″ H × 24″ W × 18″ D (860 × 620 × 460 mm).

How much does a 15 kVA oil-filled transformer weigh?

A 15 kVA oil-filled transformer weighs approximately 500 lbs (227 kg) including oil.

What is the BIL rating for a 15 kVA transformer?

The standard BIL (Basic Insulation Level) rating is 95 kV, which is standard for 12.47kv-15kv primary.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.00 – General Requirements for Liquid-Immersed Distribution Transformers
  • IEEE C57.12.90 – Test Code for Liquid-Immersed Distribution Transformers
  • IEEE C57.106 – Guide for Acceptance and Maintenance of Insulating Oil
  • NEMA TR-1 – Transformers, Regulators and Reactors
  • EPA 40 CFR 112 – SPCC Requirements

Disclaimer: Specifications shown are typical reference values. Actual specifications vary by manufacturer, voltage class, and application. Oil-filled transformers require proper containment, maintenance, and environmental compliance. Always consult manufacturer datasheets and local codes. Last updated: January 2026