30 kVA Three-Phase Transformer: Complete Specifications & Dimensions

Comprehensive technical data for 30 kVA dry transformers including dimensions, weight, full load amps, installation tips, and sizing guidance

Quick Specifications

Rated Power:30 kVAPhase:Three-Phase
Primary Voltage:480VSecondary Voltage:208Y/120V
Weight:280 lbs (127 kg)Efficiency:98.3%
Dimensions (H×W×D):35″ × 20″ × 16″ (889 × 508 × 406 mm)

A 30 kVA transformer is commonly used in Commercial buildings, HVAC systems. This guide provides complete specifications to help engineers and purchasers select and install 30 kVA transformers correctly.

⚠️ Important: Specifications shown are typical values for reference. Actual dimensions and weights vary by manufacturer. Always verify with manufacturer datasheet before ordering.

30 kVA Transformer Dimensions

30-0-kva-three-phase-transformer-dimensions
30 kVA Three-Phase Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)889 mm35″
Width (W)508 mm20″
Depth (D)406 mm16″
🔧 Installation Note: At 280 lbs, this 30 kVA transformer requires proper rigging equipment for installation. Use a pallet jack or forklift for safe positioning. Ensure floor can support the load plus any additional connected equipment weight.

30 kVA Transformer Weight

Weight TypePounds (lbs)Kilograms (kg)
Dry-Type Transformer280 lbs127 kg
Oil-Filled Equivalent*~420 lbs~190 kg
Shipping Weight (Approx.)~308 lbs~139 kg

*Oil-filled transformer weight is estimated at approximately 1.5× dry-type weight.


Full Load Amps at Various Voltages

The following table shows calculated full load amperage for a 30 kVA three-phase transformer:

VoltageFull Load AmpsSuggested Wire Size
120V144.3 A2/0 AWG
208V83.3 A#3 AWG
240V72.2 A#3 AWG
277V62.5 A#4 AWG
480V36.1 A#8 AWG
600V28.9 A#10 AWG
Formula Used:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 36.1 A = (30 × 1000) ÷ (480 × 1.732)

Electrical Specifications

ParameterValueNotes
Rated kVA30 kVAAt rated voltage and frequency
Frequency60 Hz50 Hz available on request
No-Load Loss100 WCore/iron losses (typical)
Load Loss350 WCopper losses at 100% load
Total Losses450 WAt 100% load
Impedance4.0%±7.5% tolerance per IEEE
Efficiency98.3%At 100% load
Sound Level~40 dBPer NEMA ST-20 (estimated)

⚠️ Important Considerations for 30 kVA Transformers:

  • At 30 kVA, ensure adequate ventilation clearance (minimum 3″ sides, 6″ top) for proper cooling.

When is a 30 kVA Three-Phase Transformer the Right Choice?

A 30 kVA three-phase transformer is ideal for:

  • Small manufacturing facilities with 3-phase equipment
  • Commercial kitchens with three-phase ovens
  • HVAC systems with 3-phase compressors up to 15 HP
  • Elevator and escalator power supply
  • Multi-tenant building common areas

Three-Phase Advantage: Compared to single-phase, this transformer delivers 26.0 kW at unity power factor with balanced loading across all phases.

Typical Load Examples for 30 kVA

Example load distribution for a 30 kVA installation:

Load TypeEstimated Demand
Three-phase HVAC compressor12 kVA
3-phase motors (combined)9 kVA
Lighting transformer4 kVA
Receptacle loads4 kVA

Note: Actual loads vary. Always perform a detailed load calculation for your specific application.


Related Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
15 kVA Three-Phase15 kVA Specifications →
30 kVA Three-PhaseCurrent Page
45 kVA Three-Phase45 kVA Specifications →

Frequently Asked Questions

What are the dimensions of a 30 kVA transformer?

A typical 30 kVA dry three-phase transformer measures approximately 35″ H × 20″ W × 16″ D (889 × 508 × 406 mm). Dimensions vary by manufacturer.

How much does a 30 kVA transformer weigh?

A 30 kVA dry transformer typically weighs around 280 lbs (127 kg). Oil-filled transformers of the same rating weigh approximately 420 lbs.

What is the full load amperage of a 30 kVA transformer at 480V?

At 480V, a 30 kVA three-phase transformer has a full load current of 36.1 amps.

What loads can a 30 kVA transformer handle?

A 30 kVA transformer can supply up to 30 kVA of apparent power. For typical loads with 0.85 power factor, this equals approximately 25.5 kW of real power.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.01 – General Requirements for Dry-Type Transformers
  • IEEE C57.12.91 – Test Code for Dry-Type Transformers
  • NEMA TP-1 – Guide for Determining Energy Efficiency
  • DOE 10 CFR 431 – Energy Conservation Standards

Disclaimer: Specifications shown are typical reference values compiled from multiple industry sources. Actual specifications vary significantly by manufacturer, model, enclosure type, and configuration. Always consult manufacturer datasheets for exact specifications before ordering or installation. Data accuracy verified using standard electrical engineering formulas. Last updated: January 2026