4000:5 Current Transformer (CT): Ratio Specifications & Selection Guide

Complete technical specifications for 4000:5 current transformers. This guide covers accuracy classes for metering and protection, burden ratings, physical dimensions, and application recommendations for 4000-Amp circuits.

⚡ 4000:5 CT Quick Reference

CT Ratio
4000:5
Turns Ratio
800:1
Metering Accuracy
Class 0.5
Protection Class
10P20

Understanding the 4000:5 CT Ratio

A 4000:5 current transformer reduces 4000 Amps of primary current to 5 Amps of secondary current, providing a 800:1 step-down ratio. This allows high-current circuits to be safely monitored using standard 5-Ampere meters and relays.

📐 Calculation Example

If your ammeter connected to a 4000:5 CT reads 3.5 A:

Primary Current = 3.5 A × 800 = 2800 Amps


Technical Specifications for 4000:5 CTs

CT Ratio4000:5 (800:1)
Primary Current Rating4000 ASecondary Current5 A
Metering Accuracy ClassClass 0.5Protection Accuracy Class10P20
Burden Rating30.0 VAKnee Point Voltage (est.)~1800 V
Window Size (typical)5.0″ diameterCT TypeBar Type
Frequency50/60 HzInsulation Class0.6 kV (LV)

Accuracy Class Explained

Metering Class 0.5:

Standard metering accuracy (IEC Class 0.5). ±0.5% ratio error at rated current. Common for energy management.

Protection Class 10P20:

Protection class (IEC 10P20). Maintains 10% composite error up to 20× rated current. Used for high-fault-current applications.

Burden Rating: 30.0 VA

High burden (30.0 VA). Designed for older electromechanical meters or long cable runs typical in 4000A+ applications.

⚠️ Critical Safety Note: Never open-circuit the secondary winding of an energized CT. This can generate dangerous high voltages (1800V+ at rated current) and damage the CT due to core saturation.

Application Guide for 4000:5 CTs

Category: Utility & High-CapacityPower plant outputs large utility substations

Typical Use Cases

  • Utility-grade revenue metering
  • High voltage substation monitoring
  • Power plant output measurement
  • Grid interconnection points

CT Selection Considerations

When to Choose 4000:5 Ratio

  • Load Current: Use when expected maximum load is 2400 – 4000 Amps. The CT should be sized so normal operating current is 60-80% of CT rating for optimal accuracy.
  • Conductor Size: This CT has a 5.0″ window, suitable for conductors up to approximately 2500 MCM or 12″ bus bar.
  • Turns Ratio: 800:1 reduction. Secondary current = Primary / 800.

When to Choose Adjacent Ratios Instead

ConditionRecommended RatioReason
Load is typically below 2000A3500:5Operating at higher % of CT rating improves accuracy at lower currents
Load may exceed 4000A occasionally4500:5Prevents CT saturation during peak loads or motor inrush
Conductor won’t fit 5.0″ windowLarger window CT or Split-CoreConsider split-core for retrofit without de-energizing

Frequently Asked Questions about 4000:5 CTs

❓ What does a 4000:5 CT ratio mean?

A 4000:5 current transformer has a turns ratio of 800:1. When 4000 Amps flows through the primary conductor, the CT outputs 5 Amps in the secondary circuit. This step-down allows safe measurement with standard 5A meters.

❓ How do I calculate the primary current from the secondary reading on a 4000:5 CT?

Multiply the secondary ammeter reading by the turns ratio (800).
Formula: Primary Amps = Secondary Amps × 800
Example: If the meter reads 2.5A, the primary current is 2.5 × 800 = 2000 Amps.

❓ Can I use a 4000:5 CT with a 1A secondary meter?

Yes, but you’ll need a 4000:1 CT instead of 4000:5. Alternatively, use a 5:1 auxiliary CT to step down the 5A secondary to 1A. The 1A secondary is common in IEC standards and allows for longer cable runs with less voltage drop.

❓ What happens if the primary current exceeds 4000A?

The CT may saturate, causing non-linear output and inaccurate readings. For protection CTs (Class 5P20), the CT is designed to maintain accuracy up to 20× rated current (80000A) for fault detection. For metering, sustained overcurrent should be avoided.

Compliance & Standards

Current transformers should comply with the following industry standards for accuracy and safety. For official standard documents, visit IEC or IEEE.

  • IEC 61869-2: Instrument transformers – Part 2: Additional requirements for current transformers
  • IEEE C57.13: IEEE Standard Requirements for Instrument Transformers
  • ANSI C12.1: American National Standard for Electric Meters – Code for Electricity Metering
  • IEC 60044-1: Instrument transformers – Part 1: Current transformers (superseded by IEC 61869)
  • NIST Handbook 44: Specifications for Current Transformers Used in Metering

For more background on current transformer principles, see the Wikipedia article on Current Transformers.


Explore Related CT Ratios

← 3000:5 CT4000:5 (Current)5000:5 CT →

Related Resources

📝 About This Guide

This technical specification guide is compiled by the Transformer4U Engineering Team, drawing from industry standards (IEC 61869-2, IEEE C57.13) and manufacturer datasheets.

Disclaimer: Specifications shown are typical values. Actual specifications vary by manufacturer and model. Always verify with the specific CT datasheet. Last updated: January 2026

Scroll to Top