750 kVA Three-Phase Transformer: Complete Specifications & Dimensions

Comprehensive technical data for 750 kVA dry transformers including dimensions, weight, full load amps, installation tips, and sizing guidance

Quick Specifications

Rated Power:750 kVAPhase:Three-Phase
Primary Voltage:480VSecondary Voltage:208Y/120V
Weight:2500 lbs (1134 kg)Efficiency:99.2%
Dimensions (H×W×D):70″ × 40″ × 35″ (1778 × 1016 × 889 mm)

A 750 kVA transformer is commonly used in Major power distribution. This guide provides complete specifications to help engineers and purchasers select and install 750 kVA transformers correctly.

⚠️ Important: Specifications shown are typical values for reference. Actual dimensions and weights vary by manufacturer. Always verify with manufacturer datasheet before ordering.

750 kVA Transformer Dimensions

750-0-kva-three-phase-transformer-dimensions
750 kVA Three-Phase Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)1778 mm70″
Width (W)1016 mm40″
Depth (D)889 mm35″
🔧 Installation Note: At 2500 lbs, this 750 kVA transformer is a major installation requiring crane service and specialized rigging. Coordinate with structural engineer for concrete pad design. Plan for extended lead times and specialized transportation requirements.

750 kVA Transformer Weight

Weight TypePounds (lbs)Kilograms (kg)
Dry-Type Transformer2500 lbs1134 kg
Oil-Filled Equivalent*~3750 lbs~1701 kg
Shipping Weight (Approx.)~2750 lbs~1247 kg

*Oil-filled transformer weight is estimated at approximately 1.5× dry-type weight.


Full Load Amps at Various Voltages

The following table shows calculated full load amperage for a 750 kVA three-phase transformer:

VoltageFull Load AmpsSuggested Wire Size
120V3608.5 A750 MCM+
208V2081.9 A750 MCM+
240V1804.3 A750 MCM+
277V1563.3 A750 MCM+
480V902.1 A750 MCM+
600V721.7 A750 MCM+
Formula Used:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 902.1 A = (750 × 1000) ÷ (480 × 1.732)

Electrical Specifications

ParameterValueNotes
Rated kVA750 kVAAt rated voltage and frequency
Frequency60 Hz50 Hz available on request
No-Load Loss750 WCore/iron losses (typical)
Load Loss3800 WCopper losses at 100% load
Total Losses4550 WAt 100% load
Impedance5.75%±7.5% tolerance per IEEE
Efficiency99.2%At 100% load
Sound Level~55 dBPer NEMA ST-20 (estimated)

⚠️ Important Considerations for 750 kVA Transformers:

  • Large transformers like this 750 kVA unit generate significant heat. Verify room ventilation capacity before installation.
  • Floor loading of 2500 lbs requires structural verification. Contact a structural engineer for slab-on-grade installations.
  • Impedance matching is critical when paralleling transformers. Consult a power systems engineer.
  • Arc flash hazard is significant at this capacity. Perform arc flash analysis and provide appropriate PPE.

When is a 750 kVA Three-Phase Transformer the Right Choice?

A 750 kVA three-phase transformer represents significant infrastructure:

  • Large industrial plants and heavy manufacturing
  • High-rise commercial buildings
  • Utility substation distribution
  • Data center primary power
  • Campus-style power distribution

Infrastructure Requirements:

  • Dedicated transformer pad or vault required
  • Primary metering typically required at this capacity
  • Coordination study with utility protection schemes essential
  • Consider on-load tap changer (OLTC) for voltage regulation

Typical Load Examples for 750 kVA

Example load distribution for a 750 kVA installation:

Load TypeEstimated Demand
Large process motors225 kVA
HVAC central plant150 kVA
Building lighting75 kVA
Elevator systems75 kVA
Production equipment150 kVA
Auxiliary loads75 kVA

Note: Actual loads vary. Always perform a detailed load calculation for your specific application.


Related Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
500 kVA Three-Phase500 kVA Specifications →
750 kVA Three-PhaseCurrent Page
1000 kVA Three-Phase1000 kVA Specifications →

Frequently Asked Questions

What are the dimensions of a 750 kVA transformer?

A typical 750 kVA dry three-phase transformer measures approximately 70″ H × 40″ W × 35″ D (1778 × 1016 × 889 mm). Dimensions vary by manufacturer.

How much does a 750 kVA transformer weigh?

A 750 kVA dry transformer typically weighs around 2500 lbs (1134 kg). Oil-filled transformers of the same rating weigh approximately 3750 lbs.

What is the full load amperage of a 750 kVA transformer at 480V?

At 480V, a 750 kVA three-phase transformer has a full load current of 902.1 amps.

What loads can a 750 kVA transformer handle?

A 750 kVA transformer can supply up to 750 kVA of apparent power. For typical loads with 0.85 power factor, this equals approximately 637.5 kW of real power.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.01 – General Requirements for Dry-Type Transformers
  • IEEE C57.12.91 – Test Code for Dry-Type Transformers
  • NEMA TP-1 – Guide for Determining Energy Efficiency
  • DOE 10 CFR 431 – Energy Conservation Standards

Disclaimer: Specifications shown are typical reference values compiled from multiple industry sources. Actual specifications vary significantly by manufacturer, model, enclosure type, and configuration. Always consult manufacturer datasheets for exact specifications before ordering or installation. Data accuracy verified using standard electrical engineering formulas. Last updated: January 2026