1500 kVA Three-Phase Transformer: Complete Specifications & Dimensions

Comprehensive technical data for 1500 kVA dry transformers including dimensions, weight, full load amps, installation tips, and sizing guidance

Quick Specifications

Rated Power:1500 kVAPhase:Three-Phase
Primary Voltage:480VSecondary Voltage:208Y/120V
Weight:4500 lbs (2041 kg)Efficiency:99.3%
Dimensions (H×W×D):84″ × 48″ × 42″ (2134 × 1219 × 1067 mm)

A 1500 kVA transformer is commonly used in Major substations. This guide provides complete specifications to help engineers and purchasers select and install 1500 kVA transformers correctly.

⚠️ Important: Specifications shown are typical values for reference. Actual dimensions and weights vary by manufacturer. Always verify with manufacturer datasheet before ordering.

1500 kVA Transformer Dimensions

1500-0-kva-three-phase-transformer-dimensions
1500 kVA Three-Phase Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)2134 mm84″
Width (W)1219 mm48″
Depth (D)1067 mm42″
🔧 Installation Note: At 4500 lbs, this 1500 kVA transformer is a major installation requiring crane service and specialized rigging. Coordinate with structural engineer for concrete pad design. Plan for extended lead times and specialized transportation requirements.

1500 kVA Transformer Weight

Weight TypePounds (lbs)Kilograms (kg)
Dry-Type Transformer4500 lbs2041 kg
Oil-Filled Equivalent*~6750 lbs~3061 kg
Shipping Weight (Approx.)~4950 lbs~2245 kg

*Oil-filled transformer weight is estimated at approximately 1.5× dry-type weight.


Full Load Amps at Various Voltages

The following table shows calculated full load amperage for a 1500 kVA three-phase transformer:

VoltageFull Load AmpsSuggested Wire Size
120V7217.1 A750 MCM+
208V4163.7 A750 MCM+
240V3608.5 A750 MCM+
277V3126.5 A750 MCM+
480V1804.3 A750 MCM+
600V1443.4 A750 MCM+
Formula Used:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 1804.3 A = (1500 × 1000) ÷ (480 × 1.732)

Electrical Specifications

ParameterValueNotes
Rated kVA1500 kVAAt rated voltage and frequency
Frequency60 Hz50 Hz available on request
No-Load Loss1200 WCore/iron losses (typical)
Load Loss6500 WCopper losses at 100% load
Total Losses7700 WAt 100% load
Impedance5.75%±7.5% tolerance per IEEE
Efficiency99.3%At 100% load
Sound Level~70 dBPer NEMA ST-20 (estimated)
⚠️ Important Considerations for 1500 kVA Transformers:

  • Large transformers like this 1500 kVA unit generate significant heat. Verify room ventilation capacity before installation.
  • Floor loading of 4500 lbs requires structural verification. Contact a structural engineer for slab-on-grade installations.
  • Impedance matching is critical when paralleling transformers. Consult a power systems engineer.
  • Arc flash hazard is significant at this capacity. Perform arc flash analysis and provide appropriate PPE.

When is a 1500 kVA Three-Phase Transformer the Right Choice?

A 1500 kVA three-phase transformer represents significant infrastructure:

  • Large industrial plants and heavy manufacturing
  • High-rise commercial buildings
  • Utility substation distribution
  • Data center primary power
  • Campus-style power distribution

Infrastructure Requirements:

  • Dedicated transformer pad or vault required
  • Primary metering typically required at this capacity
  • Coordination study with utility protection schemes essential
  • Consider on-load tap changer (OLTC) for voltage regulation

Typical Load Examples for 1500 kVA

Example load distribution for a 1500 kVA installation:

Load TypeEstimated Demand
Large process motors450 kVA
HVAC central plant300 kVA
Building lighting150 kVA
Elevator systems150 kVA
Production equipment300 kVA
Auxiliary loads150 kVA

Note: Actual loads vary. Always perform a detailed load calculation for your specific application.


Related Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
1000 kVA Three-Phase1000 kVA Specifications →
1500 kVA Three-PhaseCurrent Page
2000 kVA Three-Phase2000 kVA Specifications →

Frequently Asked Questions

What are the dimensions of a 1500 kVA transformer?

A typical 1500 kVA dry three-phase transformer measures approximately 84″ H × 48″ W × 42″ D (2134 × 1219 × 1067 mm). Dimensions vary by manufacturer.

How much does a 1500 kVA transformer weigh?

A 1500 kVA dry transformer typically weighs around 4500 lbs (2041 kg). Oil-filled transformers of the same rating weigh approximately 6750 lbs.

What is the full load amperage of a 1500 kVA transformer at 480V?

At 480V, a 1500 kVA three-phase transformer has a full load current of 1804.3 amps.

What loads can a 1500 kVA transformer handle?

A 1500 kVA transformer can supply up to 1500 kVA of apparent power. For typical loads with 0.85 power factor, this equals approximately 1275.0 kW of real power.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.01 – General Requirements for Dry-Type Transformers
  • IEEE C57.12.91 – Test Code for Dry-Type Transformers
  • NEMA TP-1 – Guide for Determining Energy Efficiency
  • DOE 10 CFR 431 – Energy Conservation Standards

Disclaimer: Specifications shown are typical reference values compiled from multiple industry sources. Actual specifications vary significantly by manufacturer, model, enclosure type, and configuration. Always consult manufacturer datasheets for exact specifications before ordering or installation. Data accuracy verified using standard electrical engineering formulas. Last updated: January 2026