2000 kVA Three-Phase Transformer: Complete Specifications & Dimensions

Comprehensive technical data for 2000 kVA dry transformers including dimensions, weight, full load amps, installation tips, and sizing guidance

Quick Specifications

Rated Power:2000 kVAPhase:Three-Phase
Primary Voltage:480VSecondary Voltage:208Y/120V
Weight:6000 lbs (2722 kg)Efficiency:99.3%
Dimensions (H×W×D):90″ × 52″ × 46″ (2286 × 1321 × 1168 mm)

A 2000 kVA transformer is commonly used in Grid infrastructure. This guide provides complete specifications to help engineers and purchasers select and install 2000 kVA transformers correctly.

⚠️ Important: Specifications shown are typical values for reference. Actual dimensions and weights vary by manufacturer. Always verify with manufacturer datasheet before ordering.

2000 kVA Transformer Dimensions

2000-0-kva-three-phase-transformer-dimensions
2000 kVA Three-Phase Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)2286 mm90″
Width (W)1321 mm52″
Depth (D)1168 mm46″
🔧 Installation Note: At 6000 lbs, this 2000 kVA transformer is a major installation requiring crane service and specialized rigging. Coordinate with structural engineer for concrete pad design. Plan for extended lead times and specialized transportation requirements.

2000 kVA Transformer Weight

Weight TypePounds (lbs)Kilograms (kg)
Dry-Type Transformer6000 lbs2722 kg
Oil-Filled Equivalent*~9000 lbs~4083 kg
Shipping Weight (Approx.)~6600 lbs~2994 kg

*Oil-filled transformer weight is estimated at approximately 1.5× dry-type weight.


Full Load Amps at Various Voltages

The following table shows calculated full load amperage for a 2000 kVA three-phase transformer:

VoltageFull Load AmpsSuggested Wire Size
120V9622.8 A750 MCM+
208V5551.6 A750 MCM+
240V4811.4 A750 MCM+
277V4168.7 A750 MCM+
480V2405.7 A750 MCM+
600V1924.6 A750 MCM+
Formula Used:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 2405.7 A = (2000 × 1000) ÷ (480 × 1.732)

Electrical Specifications

ParameterValueNotes
Rated kVA2000 kVAAt rated voltage and frequency
Frequency60 Hz50 Hz available on request
No-Load Loss1500 WCore/iron losses (typical)
Load Loss8000 WCopper losses at 100% load
Total Losses9500 WAt 100% load
Impedance5.75%±7.5% tolerance per IEEE
Efficiency99.3%At 100% load
Sound Level~80 dBPer NEMA ST-20 (estimated)

⚠️ Important Considerations for 2000 kVA Transformers:

  • Large transformers like this 2000 kVA unit generate significant heat. Verify room ventilation capacity before installation.
  • Floor loading of 6000 lbs requires structural verification. Contact a structural engineer for slab-on-grade installations.
  • Impedance matching is critical when paralleling transformers. Consult a power systems engineer.
  • Arc flash hazard is significant at this capacity. Perform arc flash analysis and provide appropriate PPE.

When is a 2000 kVA Three-Phase Transformer the Right Choice?

A 2000 kVA three-phase transformer represents significant infrastructure:

  • Large industrial plants and heavy manufacturing
  • High-rise commercial buildings
  • Utility substation distribution
  • Data center primary power
  • Campus-style power distribution

Infrastructure Requirements:

  • Dedicated transformer pad or vault required
  • Primary metering typically required at this capacity
  • Coordination study with utility protection schemes essential
  • Consider on-load tap changer (OLTC) for voltage regulation

Typical Load Examples for 2000 kVA

Example load distribution for a 2000 kVA installation:

Load TypeEstimated Demand
Large process motors600 kVA
HVAC central plant400 kVA
Building lighting200 kVA
Elevator systems200 kVA
Production equipment400 kVA
Auxiliary loads200 kVA

Note: Actual loads vary. Always perform a detailed load calculation for your specific application.


Related Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
1500 kVA Three-Phase1500 kVA Specifications →
2000 kVA Three-PhaseCurrent Page
2500 kVA Three-Phase2500 kVA Specifications →

Frequently Asked Questions

What are the dimensions of a 2000 kVA transformer?

A typical 2000 kVA dry three-phase transformer measures approximately 90″ H × 52″ W × 46″ D (2286 × 1321 × 1168 mm). Dimensions vary by manufacturer.

How much does a 2000 kVA transformer weigh?

A 2000 kVA dry transformer typically weighs around 6000 lbs (2722 kg). Oil-filled transformers of the same rating weigh approximately 9000 lbs.

What is the full load amperage of a 2000 kVA transformer at 480V?

At 480V, a 2000 kVA three-phase transformer has a full load current of 2405.7 amps.

What loads can a 2000 kVA transformer handle?

A 2000 kVA transformer can supply up to 2000 kVA of apparent power. For typical loads with 0.85 power factor, this equals approximately 1700.0 kW of real power.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.01 – General Requirements for Dry-Type Transformers
  • IEEE C57.12.91 – Test Code for Dry-Type Transformers
  • NEMA TP-1 – Guide for Determining Energy Efficiency
  • DOE 10 CFR 431 – Energy Conservation Standards

Disclaimer: Specifications shown are typical reference values compiled from multiple industry sources. Actual specifications vary significantly by manufacturer, model, enclosure type, and configuration. Always consult manufacturer datasheets for exact specifications before ordering or installation. Data accuracy verified using standard electrical engineering formulas. Last updated: January 2026