2500 kVA Three-Phase Transformer: Complete Specifications & Dimensions

Comprehensive technical data for 2500 kVA dry transformers including dimensions, weight, full load amps, installation tips, and sizing guidance

Quick Specifications

Rated Power:2500 kVAPhase:Three-Phase
Primary Voltage:480VSecondary Voltage:208Y/120V
Weight:7500 lbs (3402 kg)Efficiency:99.4%
Dimensions (H×W×D):96″ × 56″ × 50″ (2438 × 1422 × 1270 mm)

A 2500 kVA transformer is commonly used in Major power systems. This guide provides complete specifications to help engineers and purchasers select and install 2500 kVA transformers correctly.

⚠️ Important: Specifications shown are typical values for reference. Actual dimensions and weights vary by manufacturer. Always verify with manufacturer datasheet before ordering.

2500 kVA Transformer Dimensions

2500-0-kva-three-phase-transformer-dimensions
2500 kVA Three-Phase Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)2438 mm96″
Width (W)1422 mm56″
Depth (D)1270 mm50″
🔧 Installation Note: At 7500 lbs, this 2500 kVA transformer is a major installation requiring crane service and specialized rigging. Coordinate with structural engineer for concrete pad design. Plan for extended lead times and specialized transportation requirements.

2500 kVA Transformer Weight

Weight TypePounds (lbs)Kilograms (kg)
Dry-Type Transformer7500 lbs3402 kg
Oil-Filled Equivalent*~11250 lbs~5103 kg
Shipping Weight (Approx.)~8250 lbs~3742 kg

*Oil-filled transformer weight is estimated at approximately 1.5× dry-type weight.


Full Load Amps at Various Voltages

The following table shows calculated full load amperage for a 2500 kVA three-phase transformer:

VoltageFull Load AmpsSuggested Wire Size
120V12028.5 A750 MCM+
208V6939.5 A750 MCM+
240V6014.2 A750 MCM+
277V5210.9 A750 MCM+
480V3007.1 A750 MCM+
600V2405.7 A750 MCM+
Formula Used:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 3007.1 A = (2500 × 1000) ÷ (480 × 1.732)

Electrical Specifications

ParameterValueNotes
Rated kVA2500 kVAAt rated voltage and frequency
Frequency60 Hz50 Hz available on request
No-Load Loss1800 WCore/iron losses (typical)
Load Loss9500 WCopper losses at 100% load
Total Losses11300 WAt 100% load
Impedance5.75%±7.5% tolerance per IEEE
Efficiency99.4%At 100% load
Sound Level~90 dBPer NEMA ST-20 (estimated)
⚠️ Important Considerations for 2500 kVA Transformers:

  • Large transformers like this 2500 kVA unit generate significant heat. Verify room ventilation capacity before installation.
  • Floor loading of 7500 lbs requires structural verification. Contact a structural engineer for slab-on-grade installations.
  • Impedance matching is critical when paralleling transformers. Consult a power systems engineer.
  • Arc flash hazard is significant at this capacity. Perform arc flash analysis and provide appropriate PPE.

When is a 2500 kVA Three-Phase Transformer the Right Choice?

A 2500 kVA three-phase transformer represents significant infrastructure:

  • Large industrial plants and heavy manufacturing
  • High-rise commercial buildings
  • Utility substation distribution
  • Data center primary power
  • Campus-style power distribution

Infrastructure Requirements:

  • Dedicated transformer pad or vault required
  • Primary metering typically required at this capacity
  • Coordination study with utility protection schemes essential
  • Consider on-load tap changer (OLTC) for voltage regulation

Typical Load Examples for 2500 kVA

Example load distribution for a 2500 kVA installation:

Load TypeEstimated Demand
Large process motors750 kVA
HVAC central plant500 kVA
Building lighting250 kVA
Elevator systems250 kVA
Production equipment500 kVA
Auxiliary loads250 kVA

Note: Actual loads vary. Always perform a detailed load calculation for your specific application.


Related Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
2000 kVA Three-Phase2000 kVA Specifications →
2500 kVA Three-PhaseCurrent Page
2500 kVA Three-Phase2500 kVA Specifications →

Frequently Asked Questions

What are the dimensions of a 2500 kVA transformer?

A typical 2500 kVA dry three-phase transformer measures approximately 96″ H × 56″ W × 50″ D (2438 × 1422 × 1270 mm). Dimensions vary by manufacturer.

How much does a 2500 kVA transformer weigh?

A 2500 kVA dry transformer typically weighs around 7500 lbs (3402 kg). Oil-filled transformers of the same rating weigh approximately 11250 lbs.

What is the full load amperage of a 2500 kVA transformer at 480V?

At 480V, a 2500 kVA three-phase transformer has a full load current of 3007.1 amps.

What loads can a 2500 kVA transformer handle?

A 2500 kVA transformer can supply up to 2500 kVA of apparent power. For typical loads with 0.85 power factor, this equals approximately 2125.0 kW of real power.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.01 – General Requirements for Dry-Type Transformers
  • IEEE C57.12.91 – Test Code for Dry-Type Transformers
  • NEMA TP-1 – Guide for Determining Energy Efficiency
  • DOE 10 CFR 431 – Energy Conservation Standards

Disclaimer: Specifications shown are typical reference values compiled from multiple industry sources. Actual specifications vary significantly by manufacturer, model, enclosure type, and configuration. Always consult manufacturer datasheets for exact specifications before ordering or installation. Data accuracy verified using standard electrical engineering formulas. Last updated: January 2026