75 kVA Single-Phase Oil-Filled Transformer: Complete Specifications

Comprehensive specifications for 75 kVA ONAN oil-filled transformer including dimensions, weight, oil volume, and electrical data

Quick Specifications

Rated Power:75 kVAPhase:Single-Phase
Primary Voltage:7200VSecondary Voltage:120/240V
Cooling Class:ONANBIL Rating:95 kV
Weight:1200 lbs (544 kg)Oil Volume:50 gallons (189 L)
Dimensions (H×W×D):46″ × 32″ × 24″ (1170 × 820 × 620 mm)

A 75 kVA oil-filled transformer is commonly used for Industrial plants, utility distribution. This guide provides complete specifications for utility engineers, electrical contractors, and procurement professionals.

⚠️ Important: Oil-filled transformers contain flammable insulating oil. Installation must comply with NEC Article 450, NFPA 70, and local fire codes. Oil containment per EPA SPCC regulations is mandatory.

75 kVA Oil-Filled Transformer Dimensions

75-0-kva-single-phase-oil-filled-transformer-dimensions
75 kVA Single-Phase Oil-Filled Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)1170 mm46″
Width (W)820 mm32″
Depth (D)620 mm24″

🔧 Installation Note: This 75 kVA oil-filled transformer weighs 1200 lbs and contains 50 gallons of insulating oil. Required:

  • Concrete pad rated for 1800 lbs minimum
  • Oil containment per EPA SPCC requirements (110% capacity)
  • Minimum 10ft clearance from buildings for outdoor installation
  • 4-8 hour settling time before energizing

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)1200 lbs (544 kg)Includes all oil and accessories
Oil Volume50 gallons (189 L)Mineral Oil
Oil TypeMineral OilIEEE C57.106 compliant
Containment Required55 gallons110% per EPA SPCC

Electrical Specifications

ParameterValueNotes
Rated kVA75 kVAAt rated voltage and ONAN cooling
Primary Voltage7200VStandard utility distribution voltage
Secondary Voltage120/240VService voltage
Cooling ClassONANOil Natural, Air Natural
BIL Rating95 kVStandard for 12.47kV-15kV primary
No-Load Loss180 WCore losses
Load Loss700 WAt rated load
Total Losses880 WAt 100% load
Impedance4.0%Per IEEE C57.12.00
Efficiency98.8%At rated load
Sound Level~46 dBPer NEMA TR-1

Secondary Full Load Amps

Full load amperage at secondary voltage for 75 kVA single-phase transformer:

Secondary VoltageFull Load AmpsConductor Size
120V625.0 A750 MCM+
208V360.6 A500 MCM
240V312.5 A500 MCM
277V270.8 A350 MCM
480V156.2 A3/0 AWG
Formula:
Single-Phase: Amps = (kVA × 1000) ÷ Voltage
Example at 240V: 312.5 A = (75 × 1000) ÷ 240

Oil Maintenance Guidelines for 75 kVA Transformer

Proper maintenance of the 50 gallons of Mineral Oil in this transformer is critical for long-term reliability:

Maintenance TaskFrequencyPurpose
Visual Oil Level CheckMonthlyDetect leaks, ensure adequate level
Oil Sample AnalysisAnnuallyDielectric strength, dissolved gas analysis (DGA)
Oil Filtration/ReconditioningEvery 3-5 yearsRemove moisture and contaminants
Silica Gel Breather CheckQuarterlyEnsure moisture protection
Bushing InspectionAnnuallyCheck for cracks, contamination, oil leaks

⚠️ Oil Handling Safety:

  • Always use proper PPE when handling transformer oil
  • Dispose of contaminated oil according to EPA regulations
  • Never mix different oil types without compatibility testing
  • Maintain SPCC containment at all times

When to Choose a 75 kVA Oil-Filled Transformer

A 75 kVA single-phase oil-filled transformer with ONAN cooling is designed for:

  • Heavy industrial loads requiring high-voltage distribution
  • Utility substations serving commercial areas
  • Mining and petroleum industry applications
  • Remote installations with outdoor exposure
  • Applications requiring superior overload capability

Advantages of Oil-Filled at 75 kVA:

  • Better Cooling: Oil provides superior heat dissipation for high loads
  • Overload Capacity: Can handle 150% overload for short periods
  • Insulation: Oil provides excellent dielectric insulation
  • Longevity: 25-40 year service life with proper maintenance

Typical Load Distribution for 75 kVA Oil-Filled Transformer

Example utility distribution loads for a 75 kVA oil-filled transformer:

Load TypeEstimated Demand
Industrial motor loads30 kVA
Process equipment22 kVA
Lighting and HVAC11 kVA
Office/Control loads7 kVA
Miscellaneous3 kVA

Note: Utility distribution varies by application. Consult with utility engineer for specific load allocations.


Related Oil-Filled Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
50 kVA Single-Phase50 kVA Oil-Filled Specs →
75 kVA Single-PhaseCurrent Page
100 kVA Single-Phase100 kVA Oil-Filled Specs →

Frequently Asked Questions

How much oil does a 75 kVA oil-filled transformer contain?

A 75 kVA single-phase oil-filled transformer typically contains 50 gallons (189 liters) of Mineral Oil insulating oil.

What are the dimensions of a 75 kVA oil-filled transformer?

Typical dimensions are 46″ H × 32″ W × 24″ D (1170 × 820 × 620 mm).

How much does a 75 kVA oil-filled transformer weigh?

A 75 kVA oil-filled transformer weighs approximately 1200 lbs (544 kg) including oil.

What is the BIL rating for a 75 kVA transformer?

The standard BIL (Basic Insulation Level) rating is 95 kV, which is standard for 12.47kv-15kv primary.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.00 – General Requirements for Liquid-Immersed Distribution Transformers
  • IEEE C57.12.90 – Test Code for Liquid-Immersed Distribution Transformers
  • IEEE C57.106 – Guide for Acceptance and Maintenance of Insulating Oil
  • NEMA TR-1 – Transformers, Regulators and Reactors
  • EPA 40 CFR 112 – SPCC Requirements

Disclaimer: Specifications shown are typical reference values. Actual specifications vary by manufacturer, voltage class, and application. Oil-filled transformers require proper containment, maintenance, and environmental compliance. Always consult manufacturer datasheets and local codes. Last updated: January 2026