112.5 kVA Three-Phase Oil-Filled Transformer: Complete Specifications

Comprehensive specifications for 112.5 kVA ONAN oil-filled transformer including dimensions, weight, oil volume, and electrical data

Quick Specifications

Rated Power:112.5 kVAPhase:Three-Phase
Primary Voltage:12470Y/7200VSecondary Voltage:208Y/120V
Cooling Class:ONANBIL Rating:95 kV
Weight:1600 lbs (726 kg)Oil Volume:65 gallons (246 L)
Dimensions (H×W×D):51″ × 38″ × 29″ (1300 × 970 × 740 mm)

A 112.5 kVA oil-filled transformer is commonly used for Industrial facilities. This guide provides complete specifications for utility engineers, electrical contractors, and procurement professionals.

⚠️ Important: Oil-filled transformers contain flammable insulating oil. Installation must comply with NEC Article 450, NFPA 70, and local fire codes. Oil containment per EPA SPCC regulations is mandatory.

112.5 kVA Oil-Filled Transformer Dimensions

112-5-kva-three-phase-oil-filled-transformer-dimensions
112.5 kVA Three-Phase Oil-Filled Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)1300 mm51″
Width (W)970 mm38″
Depth (D)740 mm29″

🔧 Installation Note: This 112.5 kVA oil-filled transformer weighs 1600 lbs and contains 65 gallons of insulating oil. Required:

  • Concrete pad rated for 2400 lbs minimum
  • Oil containment per EPA SPCC requirements (110% capacity)
  • Minimum 10ft clearance from buildings for outdoor installation
  • 4-8 hour settling time before energizing

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)1600 lbs (726 kg)Includes all oil and accessories
Oil Volume65 gallons (246 L)Mineral Oil
Oil TypeMineral OilIEEE C57.106 compliant
Containment Required71 gallons110% per EPA SPCC

Electrical Specifications

ParameterValueNotes
Rated kVA112.5 kVAAt rated voltage and ONAN cooling
Primary Voltage12470Y/7200VStandard utility distribution voltage
Secondary Voltage208Y/120VService voltage
Cooling ClassONANOil Natural, Air Natural
BIL Rating95 kVStandard for 12.47kV-15kV primary
No-Load Loss280 WCore losses
Load Loss1100 WAt rated load
Total Losses1380 WAt 100% load
Impedance4.5%Per IEEE C57.12.00
Efficiency98.8%At rated load
Sound Level~47 dBPer NEMA TR-1

Secondary Full Load Amps

Full load amperage at secondary voltage for 112.5 kVA three-phase transformer:

Secondary VoltageFull Load AmpsConductor Size
120V541.3 A750 MCM+
208V312.3 A500 MCM
240V270.6 A350 MCM
277V234.5 A300 MCM
480V135.3 A2/0 AWG
Formula:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 135.3 A = (112.5 × 1000) ÷ (480 × 1.732)

Oil Maintenance Guidelines for 112.5 kVA Transformer

Proper maintenance of the 65 gallons of Mineral Oil in this transformer is critical for long-term reliability:

Maintenance TaskFrequencyPurpose
Visual Oil Level CheckMonthlyDetect leaks, ensure adequate level
Oil Sample AnalysisAnnuallyDielectric strength, dissolved gas analysis (DGA)
Oil Filtration/ReconditioningEvery 3-5 yearsRemove moisture and contaminants
Silica Gel Breather CheckQuarterlyEnsure moisture protection
Bushing InspectionAnnuallyCheck for cracks, contamination, oil leaks

⚠️ Oil Handling Safety:

  • Always use proper PPE when handling transformer oil
  • Dispose of contaminated oil according to EPA regulations
  • Never mix different oil types without compatibility testing
  • Maintain SPCC containment at all times

When to Choose a 112.5 kVA Three-Phase Oil-Filled Transformer

A 112.5 kVA three-phase oil-filled transformer is well-suited for:

  • Commercial building service entrance
  • Small manufacturing facilities
  • Utility distribution substations
  • Shopping centers and retail developments
  • Medium-voltage industrial applications

Cooling Class ONAN: 自然油循环、自然空气冷却

Typical Load Distribution for 112.5 kVA Oil-Filled Transformer

Example utility distribution loads for a 112.5 kVA oil-filled transformer:

Load TypeEstimated Demand
Three-phase motor loads45 kVA
HVAC systems28 kVA
Lighting transformers16 kVA
Receptacle/misc loads22 kVA

Note: Utility distribution varies by application. Consult with utility engineer for specific load allocations.


Related Oil-Filled Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
75 kVA Three-Phase75 kVA Oil-Filled Specs →
112.5 kVA Three-PhaseCurrent Page
150 kVA Three-Phase150 kVA Oil-Filled Specs →

Frequently Asked Questions

How much oil does a 112.5 kVA oil-filled transformer contain?

A 112.5 kVA three-phase oil-filled transformer typically contains 65 gallons (246 liters) of Mineral Oil insulating oil.

What are the dimensions of a 112.5 kVA oil-filled transformer?

Typical dimensions are 51″ H × 38″ W × 29″ D (1300 × 970 × 740 mm).

How much does a 112.5 kVA oil-filled transformer weigh?

A 112.5 kVA oil-filled transformer weighs approximately 1600 lbs (726 kg) including oil.

What is the BIL rating for a 112.5 kVA transformer?

The standard BIL (Basic Insulation Level) rating is 95 kV, which is standard for 12.47kv-15kv primary.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.00 – General Requirements for Liquid-Immersed Distribution Transformers
  • IEEE C57.12.90 – Test Code for Liquid-Immersed Distribution Transformers
  • IEEE C57.106 – Guide for Acceptance and Maintenance of Insulating Oil
  • NEMA TR-1 – Transformers, Regulators and Reactors
  • EPA 40 CFR 112 – SPCC Requirements

Disclaimer: Specifications shown are typical reference values. Actual specifications vary by manufacturer, voltage class, and application. Oil-filled transformers require proper containment, maintenance, and environmental compliance. Always consult manufacturer datasheets and local codes. Last updated: January 2026