CT Burden Calculation: Formula + Excel Template + Wire Sizing Guide

Step-by-step guide to calculating current transformer burden with formulas, wire sizing tables, and practical
examples

 Technical diagram showing CT burden components
CT Burden Components: Internal + Wire +Instrument

This CT burden calculation guide provides engineers with step-by-step methods to calculate
the burden
for current transformers. Proper burden calculation is essential for maintaining the
accuracy limit of your CT and ensuring reliable operation of metering and protection systems.This is part of our Complete CT Guide series.

CT burden refers to the total impedance connected to the CT secondary circuit. If
the actual burden exceeds the rated burden, the current transformer will operate beyond its accuracy
limit
, resulting in measurement errors.

💡 Key Rule: The total burden must not exceed the CT’s rated burden (in VA) to maintain specified
accuracy. A 15VA rated CT with 5A secondary current can support up to 0.6Ω total burden.

What is CT Burden?

CT burden is the total load connected to the secondary winding of a current
transformer, expressed in volt-amperes (VA) or ohms (Ω).

Burden Components

ComponentDescriptionTypical Values
CT Internal ResistanceSelf-resistance of secondary winding0.02-0.2Ω
Lead Wire ResistanceCable from CT to instrumentsDepends on length/gauge
Instrument BurdenMeters, relays, transducers0.05-5VA per device

VA vs Ohms Conversion

For 5A secondary CTs:

Burden (Ω) = Burden (VA) / I² = Burden (VA) / 25

Example: 15VA burden = 15/25 = 0.6Ω


For 1A secondary CTs:

Burden (Ω) = Burden (VA) / 1 = Burden (VA)

Example: 15VA burden = 15Ω


CT Burden Calculation Formula

Total Burden Formula

To calculate the burden for current transformers:

Total Burden (Ω) = CT Internal R + Wire R + Instrument R

Total Burden (VA) = I² × Total Burden (Ω)

Wire Resistance Calculation

Wire Burden (VA) = I² × R × L × 2

Where:

  • I = Secondary current (A)
  • R = Wire resistance (Ω/m)
  • L = One-way cable length (m)
  • 2 = Round-trip factor

Step-by-Step Calculation Example

Example: 600:5A CT with 25m Cable Run

📊 Given:

  • CT Ratio: 600:5A
  • CT Rated Burden: 15VA
  • Cable length: 25m one-way
  • Cable: 2.5mm² copper (0.00734 Ω/m)
  • Connected meter burden: 5VA
  • CT internal burden: 1VA

Step 1: Calculate Wire Burden

Wire Burden = I² × R × L × 2 = 5² × 0.00734 × 25 × 2 = 9.18VA

Step 2: Calculate Total Burden

Total Burden = CT Internal + Wire + Meter = 1VA + 9.18VA + 5VA = 15.18VA

Step 3: Compare with Rated Burden

Total Burden (15.18VA) > Rated Burden (15VA)

Result: The VA burden exceeds the CT’s rating! Solutions:

  • Use larger cable (4mm² or 6mm²)
  • Reduce cable length
  • Use 1A secondary CT instead of 5A

Wire Sizing for CT Burden

Wire Resistance Table

Wire SizeResistance (Ω/m) @ 20°C
1.5 mm²0.01210
2.5 mm²0.00734
4.0 mm²0.00461
6.0 mm²0.00308
10 mm²0.00183

Maximum Cable Length Table

CT SecondaryRated Burden1.5mm² Max2.5mm² Max4mm² Max
5A5VA3m5m9m
5A10VA7m11m17m
5A15VA10m16m26m
5A30VA20m33m52m
1A5VA83m136m217m
1A15VA250m409m650m

Professional-chart-showing-wire-sizing-for-CT-burden
Wire Sizing Chart for CT Burden Applications
Note: These values assume 2VA available for wiring after deducting instrument burden. For 1A CTs,
the burden advantage is 25× compared to 5A CTs.

Burden for Current Transformers: Selection Guide

Standard CT Burden Ratings

CT ClassStandard Burdens (VA)Accuracy Limit
0.22.5, 5, 10, 15±0.2% ratio error
0.52.5, 5, 10, 15, 30±0.5% ratio error
5P5, 10, 15, 30±1% ratio error at ALF
10P5, 10, 15, 30±3% ratio error at ALF

Typical Instrument Burdens

InstrumentTypical VA Burden
Digital meter0.05 – 0.5 VA
Analog ammeter1 – 3 VA
Protection relay0.1 – 1 VA
Watt transducer0.5 – 1 VA
Energy meter0.5 – 2 VA

1A vs 5A Secondary: Burden Comparison

When cable runs are long, consider 1A secondary CTs:

Factor5A Secondary1A Secondary
Wire burden (25m, 2.5mm²)9.18VA0.37VA
Maximum cable (15VA)~25m~600m
Meter compatibilityStandardMay need verification
CostLowerSlightly higher

For installations where CT secondary leads exceed 30m, 1A secondary CTs significantly reduce
VA burden and maintain the accuracy limit.


🏭 Factory Experience:

  1. Always Calculate Before Installation: We’ve seen many field issues where burdens were
    estimated, not calculated. The 5VA “digital meter” assumption often ignores cable burden entirely.
  2. 1A vs 5A Decision: For any cable run over 20m, seriously consider 1A secondary CTs. The
    burden advantage is 25×, making cable sizing much more forgiving.
  3. Temperature Derating: Wire resistance increases ~0.4% per °C above 20°C. In hot
    environments (40°C), add 8% to calculated wire burden.
  4. Leave Margin: We recommend keeping actual burden at 80% of rated burden. This provides
    margin for temperature effects and future additions.

Frequently Asked Questions

How do I calculate CT burden?

CT burden is calculated by summing the CT internal resistance, wire resistance, and instrument
impedance. Convert to VA using: Burden (VA) = I² × Total Resistance (Ω). For a 5A CT, this equals 25 × R.

What happens if CT burden is exceeded?

If the burden exceeds the CT’s rated value, the CT will saturate partially, causing ratio errors beyond the specified
accuracy limit. This leads to inaccurate measurements and potential protection relay malfunctions.

Why do 1A CTs have lower burden than 5A CTs?

Because burden for current transformers (VA) = I² × R, the wire burden for 1A CTs is only 1/25th of
5A CTs for the same resistance. This makes 1A CTs ideal for long cable runs.

What is a typical CT burden for digital meters?

Modern digital meters typically have very low burden of 0.05-0.5VA. However, the total burden calculation must also
include wire resistance, which often dominates in long runs.

How do I select CT burden rating?

Calculate the burden (CT + wires + instruments), add 20% safety margin, then select the next higher
standard burden rating (2.5, 5, 10, 15, or 30VA).


Related Articles


References

  1. IEC 61869-2 – Instrument Transformers: Current
    Transformers
  2. IEEE C57.13 – Standard Requirements for
    Instrument Transformers
  3. CT
    Burden Chart – Flex-Core

Disclaimer: This information is provided for educational purposes. Always verify burden calculations with CT
manufacturers and applicable standards for critical applications.

Scroll to Top