CT Accuracy Class Explained: 0.1 vs 0.2 vs 0.5 vs 5P | IEC & IEEE

Understanding metering and protection accuracy classes for current transformers according to IEC 61869-2 and IEEE
C57.13 standards

Infographic-showing-CT-accuracy-classes-divided-into-two-section
CT Accuracy Classes: Metering vs Protection

Understanding CT accuracy class explained is essential for selecting the right current transformer
for your application. The accuracy classes define how precisely a CT reproduces the primary current
in its secondary circuit, affecting measurement accuracy and protection reliability.

This guide covers both metering and protection accuracy classes according to IEC 61869-2 and IEEE
C57.13 standards, helping you choose the appropriate CT class for your specific requirements.

💡 Key Concept: A CT’s accuracy class indicates the maximum allowable error at rated conditions.
For example, a Class 0.5 CT has a maximum ratio error of ±0.5% at 100% rated current.

What is CT Accuracy Class?

CT accuracy class is a standardized rating that defines the permissible limits of ratio error and
phase displacement for a current transformer. The class determines how accurately the secondary current reflects the
primary current.

Two Main Categories

CategoryPurposeAccuracy Priority
Metering ClassesRevenue/energy meteringHighest accuracy at normal currents
Protection ClassesRelay operation during faultsAccuracy maintained during overcurrents

Metering Accuracy Classes (IEC 61869-2)

Metering accuracy classes are designed for precise current measurement under normal operating
conditions.

Standard Metering Classes

ClassRatio Error at 100% InPhase DisplacementApplication
0.1±0.1%±5 minutesPrecision laboratory
0.2±0.2%±10 minutesRevenue metering
0.2S±0.2% (extended)±10 minutesLow-load revenue metering
0.5±0.5%±30 minutesSub-metering, industrial
0.5S±0.5% (extended)±30 minutesVariable load metering
1.0±1.0%±60 minutesGeneral indication
3.0±3.0%Not specifiedApproximate indication

Error Limits at Different Currents (IEC 61869-2)

Class1% In5% In20% In100% In120% In
0.2—±0.75%±0.35%±0.2%±0.2%
0.2S±0.75%±0.35%±0.2%±0.2%±0.2%
0.5—±1.5%±0.75%±0.5%±0.5%
0.5S±1.5%±0.75%±0.5%±0.5%±0.5%
1.0—±3.0%±1.5%±1.0%±1.0%

What Does “S” Mean in 0.2S and 0.5S?

The “S” designation (Special) indicates extended accuracy at low currents:

  • Standard classes (0.2, 0.5): Accuracy guaranteed only from 5% to 120% of rated current
  • Special classes (0.2S, 0.5S): Accuracy guaranteed from 1% to 120% of rated current

This makes “S” classes ideal for variable load applications where accurate measurement at low currents is
critical.

Line-graph-comparing-Class-0.5-vs-0.5S-accuracy-limits
Class 0.5 vs 0.5S: Extended Range Accuracy Comparison

Protection Accuracy Classes (IEC 61869-2)

Protection accuracy classes ensure the CT provides reliable output during fault conditions when
currents may reach many times the rated value.

Standard Protection Classes

ClassComposite Error LimitALF OptionsApplication
5P±5%5, 10, 15, 20, 30General overcurrent protection
10P±10%5, 10, 15, 20, 30Standard protection applications
PXSpecified by user—Differential, high-impedance

Understanding 5P10, 5P20, 10P10, 10P20

The designation combines accuracy and Accuracy Limit Factor (ALF):

ClassMeaning
5P10±5% error up to 10× rated current
5P20±5% error up to 20× rated current
10P10±10% error up to 10× rated current
10P20±10% error up to 20× rated current

Example: A 100:5 CT rated 5P20 will maintain ±5% accuracy at currents up to 2000A (20 × 100A rated
primary).


IEEE C57.13 Accuracy Classes

The IEEE standard uses different designations for accuracy classes:

Metering Classes (IEEE)

ClassRatio Error LimitEquivalent IEC
0.3±0.3% at 100% In~Class 0.5
0.6±0.6% at 100% In~Class 1.0
1.2±1.2% at 100% In~Class 3.0

Relay Classes (IEEE C57.13)

ClassMeaning
C100Ratio error ≤10% up to 20× rated at 1Ω burden (100V)
C200Ratio error ≤10% up to 20× rated at 2Ω burden (200V)
C400Ratio error ≤10% up to 20× rated at 4Ω burden (400V)
C800Ratio error ≤10% up to 20× rated at 8Ω burden (800V)

How to Select the Right Accuracy Class

For Revenue Metering

Load CharacteristicRecommended Class
Constant high load0.2 or 0.5
Variable load (factories)0.2S or 0.5S
Low power factor loads0.2S (lower phase error)

For Protection Applications

Protection TypeRecommended Class
Overcurrent (50/51)5P10 or 10P10
Directional (67)5P10
Differential (87)5P20 or PX
High-impedancePX or TPX

🏭 Factory Experience:Based on our CT manufacturing experience:

  1. Don’t Over-Specify: Many customers request 0.2S class when 0.5 would suffice.
    Over-specification increases cost without benefit if load never operates below 5% rated current.
  2. Match Application to Class: Use metering classes for revenue/billing. Use protection
    classes for relays. Never use protection-class CTs for revenue metering.
  3. Consider Extended Range: For installations with highly variable loads (solar plants, EV
    chargers), the “S” classes provide significant accuracy improvement at low power levels.
  4. ALF Selection: Choose ALF based on actual fault current levels. Over-specifying ALF (e.g.,
    5P30 when 5P10 is sufficient) makes the CT larger and more expensive.

Frequently Asked Questions

What is CT accuracy class?

CT accuracy class is a standardized rating defining the maximum allowable ratio error and phase displacement. For
example, Class 0.5 means the CT’s ratio error does not exceed ±0.5% at rated current.

What is the difference between 0.5 and 0.5S class?

Class 0.5 guarantees accuracy from 5% to 120% of rated current, while 0.5S (Special) guarantees accuracy from 1% to
120%. The “S” class is more accurate at low currents.

What does 5P20 mean?

5P20 means the CT maintains ±5% composite error (the “5P”) at currents up to 20 times rated current (the “20”). This
is suitable for protection applications with high fault currents.

Can I use a metering CT for protection?

Metering CTs can become saturated during high fault currents, potentially causing relay malfunction. Always use
protection-class CTs for protection applications.

Which accuracy class is best for revenue metering?

Class 0.2 or 0.2S is recommended for revenue metering where accuracy directly affects billing. Class 0.5S is
acceptable for most industrial sub-metering applications.


Related Articles


References

  1. IEC 61869-2 – Instrument Transformers: Current
    Transformers
  2. IEEE C57.13 – Standard Requirements for
    Instrument Transformers
  3. CT Accuracy Standards
    – CTL Systems

Disclaimer: This information is provided for educational purposes. Always verify accuracy class requirements with
applicable standards and consult qualified engineers for specific applications.