2000.0 kVA Three-Phase Padmount Transformer: Complete Specifications

Comprehensive specifications for 2000.0 kVA dead-front padmount transformer including dimensions, weight, concrete pad requirements, and electrical data

Quick Specifications

Rated Power:2000.0 kVAPhase:Three-Phase
Primary Voltage:12470GY/7200Secondary Voltage:480Y/277
Enclosure:Dead-FrontCooling:ONAF
Weight:12400 lbs (5625 kg)Concrete Pad:144″ × 144″
Dimensions (H×W×D):72″ × 106″ × 80″ (1829 × 2692 × 2032 mm)

A 2000.0 kVA padmount transformer is a ground-mounted, oil-filled distribution transformer commonly used in major grid infrastructure. This guide provides complete specifications for utility engineers, electrical contractors, and facility planners.

✅ Dead-Front Design: All primary and secondary connections are made inside the locked cabinet, eliminating exposed live parts. This design meets ANSI/IEEE C57.12.28 safety standards for public areas.

2000.0 kVA Padmount Transformer Dimensions

2000-0-kva-three-phase-padmount-transformer-dimensions
2000.0 kVA Three-Phase Padmount Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)1829 mm72″
Width (W)2692 mm106″
Depth (D)2032 mm80″
🔧 Installation Note: Heavy unit (12400 lbs) – requires crane for installation. Concrete pad must be level within 1/4 inch per foot and fully cured (28 days minimum). Maintain minimum 10 feet clearance from buildings per NEC and local fire codes.

Concrete Pad Requirements

The 2000.0 kVA padmount transformer requires a properly designed concrete pad for installation:

Pad SpecificationRequirementNotes
Minimum Pad Size144″ × 144″Allow 6″ overhang on all sides
Pad Thickness4-6 inchesReinforced concrete, 3000 PSI minimum
Grade/SlopeLevel ± 1/4″/ftSlight slope away from buildings
Conduit EntryPer utility specsPrimary and secondary duct banks
Curing Time28 days minimumBefore transformer placement

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)12400 lbs (5625 kg)Includes all oil and accessories
Oil Volume647 gallons (2450 L)Mineral insulating oil
Cooling ClassONAFOil Natural, Air Forced
BIL Rating150 kVBasic Insulation Level

Electrical Specifications

ParameterValueNotes
Rated kVA2000.0 kVAAt rated voltage and ONAF cooling
Primary Voltage12470GY/7200With taps ±2.5%, ±5%
Secondary Voltage480Y/277Standard service voltage
No-Load Loss2700 WCore losses
Load Loss15500 WAt rated load
Total Losses18200 WAt 100% load
Impedance6.0%Per IEEE C57.12.00
Efficiency99.3%DOE 2016 compliant

Secondary Full Load Amps

Full load amperage at secondary voltage for 2000.0 kVA three-phase padmount transformer:

Secondary VoltageFull Load AmpsConductor Size
120V9622.8 A750+ MCM
208V5551.6 A750+ MCM
240V4811.4 A750+ MCM
277V4168.7 A750+ MCM
480V2405.7 A750+ MCM
Formula:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × √3)
Example at 240V: 4811.4 A = (2000.0 × 1000) ÷ (240 × 1.732)

When to Choose a 2000.0 kVA Padmount Transformer

This 2000.0 kVA three-phase padmount transformer is designed for major industrial facilities, utility substations, and primary distribution applications.

Typical Load Distribution for 2000.0 kVA Padmount Transformer

Load TypeEstimated Demand
Heavy industrial loads1000 kVA
HVAC chillers500 kVA
Auxiliary systems300 kVA

Note: Load estimates are typical values. Consult project load study for specific applications.


Related Padmount Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
1500.0 kVA Three-Phase1500.0 kVA Padmount Specs →
2000.0 kVA Three-PhaseCurrent Page
2500.0 kVA Three-Phase2500.0 kVA Padmount Specs →

Frequently Asked Questions

What size concrete pad do I need for a 2000.0 kVA padmount transformer?

A 2000.0 kVA padmount transformer requires a minimum pad size of 144″ × 144″ with 4-6 inches thickness of reinforced concrete.

How much does a 2000.0 kVA padmount transformer weigh?

A 2000.0 kVA padmount transformer weighs approximately 12400 lbs (5625 kg) including oil.

What is the difference between dead-front and live-front padmount transformers?

Dead-front designs (like this 2000.0 kVA unit) have all connections inside the locked cabinet with no exposed live parts. Live-front designs have bushings exposed on top, requiring additional safety barriers in public areas.