Padmount Transformer Sizing Chart: Complete kVA Selection Guide

Comprehensive sizing chart for dead-front padmount transformers. Find specifications, dimensions, concrete pad
requirements, and selection guidelines for all standard kVA ratings.


Padmount transformers are the most common type of distribution transformer used in residential subdivisions,
commercial buildings, and industrial facilities
across North America. This comprehensive sizing chart
helps engineers, contractors, and facility managers select the correct kVA rating based on load requirements and
installation constraints.

โœ… All specifications are for Dead-Front designs per IEEE C57.12.28,
suitable for installation in public areas without additional barriers.

Single-Phase Padmount Transformer Sizing Chart

Single-phase padmount transformers are typically used for residential distribution and small
commercial applications. Primary voltage: 12470GY/7200V, Secondary: 120/240V.

kVADimensions (Hร—Wร—D)Weight (lbs)Oil (gal)Pad SizeSpecs
25 kVA24″ ร— 32″ ร— 33″604 lbs30 gal44″ ร— 44″View
Details โ†’
37.5 kVA26″ ร— 34″ ร— 34″750 lbs37 gal48″ ร— 48″View
Details โ†’
50 kVA28″ ร— 36″ ร— 37″900 lbs44 gal52″ ร— 52″View
Details โ†’
75 kVA30″ ร— 38″ ร— 39″1,100 lbs56 gal56″ ร— 56″View
Details โ†’
100 kVA32″ ร— 40″ ร— 41″1,300 lbs70 gal60″ ร— 60″View
Details โ†’
167 kVA36″ ร— 44″ ร— 45″1,700 lbs95 gal68″ ร— 68″View
Details โ†’

Three-Phase Padmount Transformer Sizing Chart

Three-phase padmount transformers serve commercial buildings, industrial facilities, and utility
substations
. Primary voltage: 12470GY/7200V.

kVADimensions (Hร—Wร—D)Weight (lbs)Oil (gal)Pad SizeSecondarySpecs
75 kVA36″ ร— 50″ ร— 44″1,400 lbs58 gal60″ ร— 60″208Y/120VDetails
โ†’
112.5 kVA38″ ร— 54″ ร— 46″1,800 lbs78 gal66″ ร— 66″208Y/120VDetails
โ†’
150 kVA40″ ร— 58″ ร— 48″2,150 lbs100 gal72″ ร— 72″208Y/120VDetails
โ†’
225 kVA42″ ร— 62″ ร— 50″2,600 lbs130 gal78″ ร— 78″208Y/120VDetails
โ†’
300 kVA44″ ร— 66″ ร— 52″3,100 lbs156 gal84″ ร— 84″208Y/120VDetails
โ†’
500 kVA48″ ร— 74″ ร— 56″4,200 lbs225 gal96″ ร— 96″480Y/277VDetails
โ†’
750 kVA54″ ร— 82″ ร— 62″5,600 lbs290 gal108″ ร— 108″480Y/277VDetails
โ†’
1000 kVA60″ ร— 90″ ร— 68″7,200 lbs370 gal120″ ร— 120″480Y/277VDetails
โ†’
1500 kVA66″ ร— 98″ ร— 74″9,600 lbs502 gal132″ ร— 132″480Y/277VDetails
โ†’
2000 kVA72″ ร— 106″ ร— 80″12,400 lbs647 gal144″ ร— 144″480Y/277VDetails
โ†’
2500 kVA78″ ร— 114″ ร— 86″15,300 lbs780 gal156″ ร— 156″480Y/277VDetails
โ†’

Concrete Pad Requirements by kVA

Every padmount transformer requires a properly designed concrete foundation pad. The pad must be
level, reinforced, and fully cured before transformer installation.

kVA RangeMinimum Pad SizePad ThicknessConcrete StrengthCuring Time
25-50 kVA44″ ร— 44″ to 52″ ร— 52″4 inches3,000 PSI28 days
75-167 kVA56″ ร— 56″ to 68″ ร— 68″4-5 inches3,000 PSI28 days
225-500 kVA78″ ร— 78″ to 96″ ร— 96″5-6 inches3,500 PSI28 days
750-2500 kVA108″ ร— 108″ to 156″ ร— 156″6-8 inches4,000 PSI28 days
โš ๏ธ Important: Always allow 6″ overhang on all sides of the transformer footprint. Verify conduit
routing and duct bank locations with utility before pouring concrete.

How to Select the Right Padmount Transformer Size

Step 1: Calculate Total Connected Load

Add up all electrical loads that will be served by the transformer:

  • HVAC systems (largest load, consider starting current)
  • Lighting and receptacles
  • Motors and machinery
  • Future expansion (typically 20-25% reserve)

Step 2: Apply Demand Factor

Not all loads operate simultaneously. Apply appropriate demand factors:

ApplicationTypical Demand Factor
Residential40-60%
Commercial Office60-70%
Retail/Restaurant70-80%
Industrial70-85%
Data Center80-90%

Step 3: Select Transformer Size

Formula: Required kVA = (Total Connected Load ร— Demand Factor) รท Power Factor

Select the next standard size above your calculated requirement to allow for load growth.

Example: A commercial building has 180 kVA connected load with 70% demand factor and 0.9 power
factor.
Required kVA = (180 ร— 0.70) รท 0.9 = 140 kVA โ†’ Select 150 kVA three-phase padmount

Frequently Asked Questions

What is the most common padmount transformer size?

For residential subdivisions, 25-50 kVA single-phase units are most common. For commercial
buildings
, 150-300 kVA three-phase is typical.

How much does a padmount transformer weigh?

Weights range from 604 lbs (25 kVA) to over 15,000 lbs (2500 kVA). Heavy units
(>2000 lbs) require crane installation.

What voltage do padmount transformers use?

Most utility padmounts use 12470GY/7200V or 24940GY/14400V primary. Secondary is typically
120/240V (single-phase) or 208Y/120V / 480Y/277V (three-phase).


Related Resources

๐Ÿ“Š More Reference Charts:


Standards & References


Disclaimer: Specifications shown are typical reference values per IEEE standards. Actual specifications vary by
manufacturer. Always consult manufacturer datasheets and local utility requirements. Last updated: January
2026