CT Knee Point Voltage Test: Step-by-Step Procedure + Results Analysis

Step-by-step guide to performing knee point voltage tests on protection-class current transformers

ct saturation causes & prevention
CT Excitation Curve: Knee Point Marks Onset of Saturation

CT knee point voltage testing is a critical procedure for verifying the performance of
protection-class current transformers. The knee point voltage (Vk) indicates the saturation characteristic of the CT
core, which directly affects protection relay operation during fault conditions.For CT fundamentals, see our Complete CT Guide.

This guide covers the complete CT knee point voltage testing procedure, including both IEC and ANSI
test methods, test equipment requirements, and result interpretation.

💡 Key Definition: The knee point voltage is the point on the CT excitation curve where a 10%
increase in voltage causes a 50% increase in excitation current (IEC definition). This marks the onset of core
saturation.

What is Knee Point Voltage?

Knee point voltage (Vk) is the voltage applied to the CT secondary terminals (with primary
open-circuited) at which the CT core begins to saturate. Above this point, the CT can no longer accurately transform
the primary current.

Why Knee Point Matters

ApplicationImportance
Differential ProtectionBoth CTs must have matching Vk for balanced operation
REF ProtectionAdequate Vk ensures proper operation during internal faults
High-Impedance ProtectionVk must exceed calculated stability voltage
Distance ProtectionPrevents CT saturation during zone 1 faults

Knee Point Formula

Vk ≥ If × (Rct + Rl + Rr)

Where:

  • If = Maximum fault current (secondary)
  • Rct = CT secondary winding resistance
  • Rl = Lead wire resistance (round trip)
  • Rr = Relay burden resistance

IEC vs ANSI Knee Point Definitions

IEC 61869-2 Definition

The knee point is defined as the voltage at which a 10% increase in voltage causes a 50% increase in
excitation current
.

ANSI C57.13 Definitions

CT TypeDefinition
Non-Gapped CorePoint where tangent line forms 45° angle with horizontal
Air-Gapped CorePoint where tangent line forms 30° angle with horizontal

Comparison Chart

StandardMethodApplication
IEC 61869-210%/50% voltage-current relationshipInternational standard
ANSI 45°Tangent line on log-log plotUS, non-gapped CTs
ANSI 30°Tangent line on log-log plotUS, gapped CTs

CT Knee Point Voltage Testing Procedure

Equipment Required

EquipmentSpecification
Variable AC source0-2000V, 50/60Hz, adjustable
VoltmeterTrue RMS, 0.5% accuracy
AmmeterRange 1mA-10A, 0.5% accuracy
Test leadsRated for test voltage
Safety equipmentInsulated gloves, barriers

Step-by-Step Test Procedure

Step 1: Safety Preparation

  • Isolate CT from system
  • Ground CT primary winding
  • Short-circuit all unused secondary windings

Step 2: Connect Test Equipment

Technical diagram showing CT knee point voltage test setup

Step 3: Perform Excitation Test

  1. Start with zero voltage
  2. Gradually increase voltage in small steps
  3. Record voltage (V) and excitation current (Ie) at each step
  4. Continue until current increases rapidly (past knee point)
  5. Reduce voltage to zero before disconnecting

Data Recording Table

StepVoltage (V)Current (mA)Notes
1102.1Linear region
2204.3Linear region
35011Linear region
410024Approaching knee
515042Near knee point
618085Knee point
7200180Saturation region

Interpreting Test Results

Determining Knee Point (IEC Method)

  1. Plot voltage vs. current on log-log graph
  2. Find the point where:
    • V2 = V1 × 1.10 (10% increase)
    • I2 = I1 × 1.50 (50% increase)
  3. This intersection defines Vk

Acceptance Criteria

ParameterRequirement
Knee Point Voltage≥ Specified Vk on nameplate
Excitation Current at Vk/2≤ Specified Ie on nameplate
Curve ShapeSmooth, no discontinuities

Troubleshooting Failed Tests

IssuePossible CauseAction
Low VkShorted turns in windingReplace CT
High IeCore degradationInvestigate further
Erratic curvePoor test connectionsCheck connections, retest
No clear kneeAir-gapped core (normal)Use ANSI 30° method

PS Class Current Transformers

Protection Special (PS) class CTs are specified by:

ParameterSymbolMeaning
Knee Point VoltageVkMinimum voltage at knee point
Excitation CurrentIeMaximum current at Vk/2
Secondary ResistanceRctMaximum DC resistance at 75°C
Example PS Class Designation:
CT Rating: 1000/1A, PS Class, Vk ≥ 650V, Ie ≤ 30mA at Vk/2This means knee point voltage must be at least 650V, and at 325V (Vk/2), excitation current must not exceed 30mA.

DC Saturation Testing Method

For CTs with very high knee point voltage, DC testing is an alternative:

Advantages of DC Testing

  • Lower voltage source required
  • Smaller, lighter test equipment
  • Can test very high Vk CTs
⚠️ Important: You MUST demagnetize the CT after DC testing. Apply gradually
reducing AC voltage (from above Vk to zero) to remove residual magnetism before returning CT to service.

🏭 Factory Experience:

  1. Always Ground Primary: During knee point testing, the CT primary must be solidly grounded.
    Floating primary can cause dangerous voltages.
  2. Demagnetization After Testing: The CT core may retain residual magnetism after testing.
    Apply gradually reducing AC voltage to demagnetize.
  3. Matching CTs for Differential: When testing CT pairs for differential protection, both CTs
    should have Vk within ±10% of each other and similar excitation characteristics.
  4. Temperature Effects: CT resistance increases with temperature. For accurate comparison with
    nameplate values, correct Rct to 75°C reference temperature.

Frequently Asked Questions

What is CT knee point voltage?

Knee point voltage (Vk) is the voltage applied to CT secondary terminals at which the core begins to saturate. Per
IEC 61869-2, it’s defined as the voltage where a 10% increase causes a 50% increase in excitation current.

Why is knee point voltage testing important?

CT knee point voltage testing verifies that the CT will perform correctly during fault conditions.
If Vk is too low, the CT may saturate during faults, causing incorrect relay operation.

What is the difference between IEC and ANSI knee point?

IEC uses a 10%/50% voltage-current definition, while ANSI uses tangent line methods (45° for non-gapped cores, 30°
for gapped cores). The resulting Vk values may differ by 10-20%.

What is PS class in current transformers?

PS (Protection Special) class specifies a CT by its knee point voltage (Vk) and excitation current (Ie) rather than
by accuracy class. It’s used for differential and high-impedance protection schemes.

How do I calculate required knee point voltage?

Calculate Vk ≥ If(sec) × (Rct + 2Rl + Rr), where If(sec) is maximum secondary fault current, Rct is CT resistance, Rl
is lead resistance per conductor, and Rr is relay burden.


Related Articles


References

  1. IEC 61869-2 – Instrument Transformers: Current
    Transformers
  2. IEEE C57.13 – Standard Requirements for
    Instrument Transformers
  3. Megger – What is a Knee Point?

Disclaimer: This information is provided for educational purposes. Always follow applicable standards and
manufacturer guidelines when performing CT testing. High voltages are involved – only qualified personnel should
conduct these tests.