500 kVA Three-Phase Transformer: Complete Specifications & Dimensions

Comprehensive technical data for 500 kVA dry transformers including dimensions, weight, full load amps, installation tips, and sizing guidance

Quick Specifications

Rated Power:500 kVAPhase:Three-Phase
Primary Voltage:480VSecondary Voltage:208Y/120V
Weight:1900 lbs (862 kg)Efficiency:99.1%
Dimensions (H×W×D):64″ × 36″ × 32″ (1626 × 914 × 813 mm)

A 500 kVA transformer is commonly used in Large industrial, utility. This guide provides complete specifications to help engineers and purchasers select and install 500 kVA transformers correctly.

⚠️ Important: Specifications shown are typical values for reference. Actual dimensions and weights vary by manufacturer. Always verify with manufacturer datasheet before ordering.

500 kVA Transformer Dimensions

500-0-kva-three-phase-transformer-dimensions
500 kVA Three-Phase Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)1626 mm64″
Width (W)914 mm36″
Depth (D)813 mm32″
🔧 Installation Note: At 1900 lbs, this 500 kVA transformer is a major installation requiring crane service and specialized rigging. Coordinate with structural engineer for concrete pad design. Plan for extended lead times and specialized transportation requirements.

500 kVA Transformer Weight

Weight TypePounds (lbs)Kilograms (kg)
Dry-Type Transformer1900 lbs862 kg
Oil-Filled Equivalent*~2850 lbs~1293 kg
Shipping Weight (Approx.)~2090 lbs~948 kg

*Oil-filled transformer weight is estimated at approximately 1.5× dry-type weight.


Full Load Amps at Various Voltages

The following table shows calculated full load amperage for a 500 kVA three-phase transformer:

VoltageFull Load AmpsSuggested Wire Size
120V2405.7 A750 MCM+
208V1387.9 A750 MCM+
240V1202.8 A750 MCM+
277V1042.2 A750 MCM+
480V601.4 A750 MCM+
600V481.1 A750 MCM+
Formula Used:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 601.4 A = (500 × 1000) ÷ (480 × 1.732)

Electrical Specifications

ParameterValueNotes
Rated kVA500 kVAAt rated voltage and frequency
Frequency60 Hz50 Hz available on request
No-Load Loss580 WCore/iron losses (typical)
Load Loss2800 WCopper losses at 100% load
Total Losses3380 WAt 100% load
Impedance5.75%±7.5% tolerance per IEEE
Efficiency99.1%At 100% load
Sound Level~50 dBPer NEMA ST-20 (estimated)
⚠️ Important Considerations for 500 kVA Transformers:

  • Large transformers like this 500 kVA unit generate significant heat. Verify room ventilation capacity before installation.
  • Floor loading of 1900 lbs requires structural verification. Contact a structural engineer for slab-on-grade installations.
  • Impedance matching is critical when paralleling transformers. Consult a power systems engineer.
  • Arc flash hazard is significant at this capacity. Perform arc flash analysis and provide appropriate PPE.

When is a 500 kVA Three-Phase Transformer the Right Choice?

A 500 kVA three-phase transformer represents significant infrastructure:

  • Large industrial plants and heavy manufacturing
  • High-rise commercial buildings
  • Utility substation distribution
  • Data center primary power
  • Campus-style power distribution

Infrastructure Requirements:

  • Dedicated transformer pad or vault required
  • Primary metering typically required at this capacity
  • Coordination study with utility protection schemes essential
  • Consider on-load tap changer (OLTC) for voltage regulation

Typical Load Examples for 500 kVA

Example load distribution for a 500 kVA installation:

Load TypeEstimated Demand
Process motors175 kVA
HVAC chillers125 kVA
Lighting systems60 kVA
Welding equipment75 kVA
Support systems65 kVA

Note: Actual loads vary. Always perform a detailed load calculation for your specific application.


Related Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
300 kVA Three-Phase300 kVA Specifications →
500 kVA Three-PhaseCurrent Page
750 kVA Three-Phase750 kVA Specifications →

Frequently Asked Questions

What are the dimensions of a 500 kVA transformer?

A typical 500 kVA dry three-phase transformer measures approximately 64″ H × 36″ W × 32″ D (1626 × 914 × 813 mm). Dimensions vary by manufacturer.

How much does a 500 kVA transformer weigh?

A 500 kVA dry transformer typically weighs around 1900 lbs (862 kg). Oil-filled transformers of the same rating weigh approximately 2850 lbs.

What is the full load amperage of a 500 kVA transformer at 480V?

At 480V, a 500 kVA three-phase transformer has a full load current of 601.4 amps.

What loads can a 500 kVA transformer handle?

A 500 kVA transformer can supply up to 500 kVA of apparent power. For typical loads with 0.85 power factor, this equals approximately 425.0 kW of real power.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.01 – General Requirements for Dry-Type Transformers
  • IEEE C57.12.91 – Test Code for Dry-Type Transformers
  • NEMA TP-1 – Guide for Determining Energy Efficiency
  • DOE 10 CFR 431 – Energy Conservation Standards

Disclaimer: Specifications shown are typical reference values compiled from multiple industry sources. Actual specifications vary significantly by manufacturer, model, enclosure type, and configuration. Always consult manufacturer datasheets for exact specifications before ordering or installation. Data accuracy verified using standard electrical engineering formulas. Last updated: January 2026