15 kVA Single-Phase Oil-Filled Transformer: Complete Specifications

Comprehensive specifications for 15 kVA ONAN oil-filled transformer including dimensions, weight, oil volume, and electrical data

Quick Specifications

Rated Power:15 kVAPhase:Single-Phase
Primary Voltage:7200VSecondary Voltage:120/240V
Cooling Class:ONANBIL Rating:60 kV
Weight:400 lbs (182 kg)Oil Volume:20 gallons (76 L)
Dimensions (H×W×D):32″ × 23″ × 16″ (820 × 580 × 410 mm)

A 15 kVA oil-filled transformer is commonly used for Residential areas, farms. This guide provides complete specifications for utility engineers, electrical contractors, and procurement professionals.

⚠️ Important: Oil-filled transformers contain flammable insulating oil. Installation must comply with NEC Article 450, NFPA 70, and local fire codes. Oil containment per EPA SPCC regulations is mandatory.

15 kVA Oil-Filled Transformer Dimensions

15 kVA Single-Phase Oil-Filled Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)820 mm32″
Width (W)580 mm23″
Depth (D)410 mm16″
🔧 Installation Note: At 400 lbs with 20 gallons of oil, this 15 kVA oil-filled transformer requires forklift positioning. Ensure oil containment provisions are in place per local environmental codes. Allow transformer to settle for 4-8 hours before energizing.

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)400 lbs (182 kg)Includes all oil and accessories
Oil Volume20 gallons (76 L)Mineral Oil
Oil TypeMineral OilIEEE C57.106 compliant
Containment Required22 gallons110% per EPA SPCC

Electrical Specifications

ParameterValueNotes
Rated kVA15 kVAAt rated voltage and ONAN cooling
Primary Voltage7200VStandard utility distribution voltage
Secondary Voltage120/240VService voltage
Cooling ClassONANOil Natural, Air Natural
BIL Rating60 kVStandard for 2.4kV-7.2kV primary
No-Load Loss60 WCore losses
Load Loss200 WAt rated load
Total Losses260 WAt 100% load
Impedance3.0%Per IEEE C57.12.00
Efficiency98.2%At rated load
Sound Level~45 dBPer NEMA TR-1

Secondary Full Load Amps

Full load amperage at secondary voltage for 15 kVA single-phase transformer:

Secondary VoltageFull Load AmpsConductor Size
120V125.0 A1/0 AWG
208V72.1 A#3 AWG
240V62.5 A#4 AWG
277V54.2 A#6 AWG
480V31.2 A#8 AWG
Formula:
Single-Phase: Amps = (kVA × 1000) ÷ Voltage
Example at 240V: 62.5 A = (15 × 1000) ÷ 240

Oil Maintenance Guidelines for 15 kVA Transformer

Proper maintenance of the 20 gallons of Mineral Oil in this transformer is critical for long-term reliability:

Maintenance TaskFrequencyPurpose
Visual Oil Level CheckMonthlyDetect leaks, ensure adequate level
Oil Sample AnalysisAnnuallyDielectric strength, dissolved gas analysis (DGA)
Oil Filtration/ReconditioningEvery 3-5 yearsRemove moisture and contaminants
Silica Gel Breather CheckQuarterlyEnsure moisture protection
Bushing InspectionAnnuallyCheck for cracks, contamination, oil leaks
⚠️ Oil Handling Safety:

  • Always use proper PPE when handling transformer oil
  • Dispose of contaminated oil according to EPA regulations
  • Never mix different oil types without compatibility testing
  • Maintain SPCC containment at all times

When to Choose a 15 kVA Oil-Filled Transformer

A 15 kVA single-phase oil-filled transformer is ideal for:

  • Utility distribution in residential neighborhoods
  • Rural electrification projects with overhead lines
  • Agricultural operations requiring reliable power
  • Outdoor installations where dry-type is not suitable
  • Applications requiring 7200V or 14.4kV primary voltage

Oil-Filled vs Dry-Type Comparison:

FactorOil-FilledDry-Type
CostLower initial costHigher initial cost
EfficiencyHigher (less losses)Slightly lower
MaintenanceOil testing requiredMinimal maintenance
LocationOutdoor preferredIndoor or outdoor
Fire RiskHigher (contain oil)Lower

Typical Load Distribution for 15 kVA Oil-Filled Transformer

Example utility distribution loads for a 15 kVA oil-filled transformer:

Load TypeEstimated Demand
Residential homes (5-15 homes)9 kVA
Street lighting2 kVA
Small commercial loads3 kVA
Agricultural pumps0 kVA

Note: Utility distribution varies by application. Consult with utility engineer for specific load allocations.


Related Oil-Filled Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
10 kVA Single-Phase10 kVA Oil-Filled Specs →
15 kVA Single-PhaseCurrent Page
25 kVA Single-Phase25 kVA Oil-Filled Specs →

Frequently Asked Questions

How much oil does a 15 kVA oil-filled transformer contain?

A 15 kVA single-phase oil-filled transformer typically contains 20 gallons (76 liters) of Mineral Oil insulating oil.

What are the dimensions of a 15 kVA oil-filled transformer?

Typical dimensions are 32″ H × 23″ W × 16″ D (820 × 580 × 410 mm).

How much does a 15 kVA oil-filled transformer weigh?

A 15 kVA oil-filled transformer weighs approximately 400 lbs (182 kg) including oil.

What is the BIL rating for a 15 kVA transformer?

The standard BIL (Basic Insulation Level) rating is 60 kV, which is standard for 2.4kv-7.2kv primary.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.00 – General Requirements for Liquid-Immersed Distribution Transformers
  • IEEE C57.12.90 – Test Code for Liquid-Immersed Distribution Transformers
  • IEEE C57.106 – Guide for Acceptance and Maintenance of Insulating Oil
  • NEMA TR-1 – Transformers, Regulators and Reactors
  • EPA 40 CFR 112 – SPCC Requirements

Disclaimer: Specifications shown are typical reference values. Actual specifications vary by manufacturer, voltage class, and application. Oil-filled transformers require proper containment, maintenance, and environmental compliance. Always consult manufacturer datasheets and local codes. Last updated: January 2026