150 kVA Three-Phase Oil-Filled Transformer: Complete Specifications

Comprehensive specifications for 150 kVA ONAN oil-filled transformer including dimensions, weight, oil volume, and electrical data

Quick Specifications

Rated Power:150 kVAPhase:Three-Phase
Primary Voltage:12470Y/7200VSecondary Voltage:208Y/120V
Cooling Class:ONANBIL Rating:95 kV
Weight:1900 lbs (862 kg)Oil Volume:80 gallons (303 L)
Dimensions (H×W×D):55″ × 41″ × 32″ (1400 × 1050 × 810 mm)

A 150 kVA oil-filled transformer is commonly used for Heavy industrial loads. This guide provides complete specifications for utility engineers, electrical contractors, and procurement professionals.

⚠️ Important: Oil-filled transformers contain flammable insulating oil. Installation must comply with NEC Article 450, NFPA 70, and local fire codes. Oil containment per EPA SPCC regulations is mandatory.

150 kVA Oil-Filled Transformer Dimensions

150-0-kva-three-phase-oil-filled-transformer-dimensions
150 kVA Three-Phase Oil-Filled Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)1400 mm55″
Width (W)1050 mm41″
Depth (D)810 mm32″

🔧 Installation Note: This 150 kVA oil-filled transformer weighs 1900 lbs and contains 80 gallons of insulating oil. Required:

  • Concrete pad rated for 2850 lbs minimum
  • Oil containment per EPA SPCC requirements (110% capacity)
  • Minimum 10ft clearance from buildings for outdoor installation
  • 4-8 hour settling time before energizing

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)1900 lbs (862 kg)Includes all oil and accessories
Oil Volume80 gallons (303 L)Mineral Oil
Oil TypeMineral OilIEEE C57.106 compliant
Containment Required88 gallons110% per EPA SPCC

Electrical Specifications

ParameterValueNotes
Rated kVA150 kVAAt rated voltage and ONAN cooling
Primary Voltage12470Y/7200VStandard utility distribution voltage
Secondary Voltage208Y/120VService voltage
Cooling ClassONANOil Natural, Air Natural
BIL Rating95 kVStandard for 12.47kV-15kV primary
No-Load Loss350 WCore losses
Load Loss1350 WAt rated load
Total Losses1700 WAt 100% load
Impedance5.0%Per IEEE C57.12.00
Efficiency98.9%At rated load
Sound Level~48 dBPer NEMA TR-1

Secondary Full Load Amps

Full load amperage at secondary voltage for 150 kVA three-phase transformer:

Secondary VoltageFull Load AmpsConductor Size
120V721.7 A750 MCM+
208V416.4 A750 MCM+
240V360.9 A500 MCM
277V312.7 A500 MCM
480V180.4 A4/0 AWG
Formula:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × 1.732)
Example at 480V: 180.4 A = (150 × 1000) ÷ (480 × 1.732)

Oil Maintenance Guidelines for 150 kVA Transformer

Proper maintenance of the 80 gallons of Mineral Oil in this transformer is critical for long-term reliability:

Maintenance TaskFrequencyPurpose
Visual Oil Level CheckMonthlyDetect leaks, ensure adequate level
Oil Sample AnalysisAnnuallyDielectric strength, dissolved gas analysis (DGA)
Oil Filtration/ReconditioningEvery 3-5 yearsRemove moisture and contaminants
Silica Gel Breather CheckQuarterlyEnsure moisture protection
Bushing InspectionAnnuallyCheck for cracks, contamination, oil leaks

⚠️ Oil Handling Safety:

  • Always use proper PPE when handling transformer oil
  • Dispose of contaminated oil according to EPA regulations
  • Never mix different oil types without compatibility testing
  • Maintain SPCC containment at all times

When to Choose a 150 kVA Three-Phase Oil-Filled Transformer

A 150 kVA three-phase oil-filled transformer is well-suited for:

  • Commercial building service entrance
  • Small manufacturing facilities
  • Utility distribution substations
  • Shopping centers and retail developments
  • Medium-voltage industrial applications

Cooling Class ONAN: 自然油循环、自然空气冷却

Typical Load Distribution for 150 kVA Oil-Filled Transformer

Example utility distribution loads for a 150 kVA oil-filled transformer:

Load TypeEstimated Demand
Three-phase motor loads60 kVA
HVAC systems37 kVA
Lighting transformers22 kVA
Receptacle/misc loads30 kVA

Note: Utility distribution varies by application. Consult with utility engineer for specific load allocations.


Related Oil-Filled Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
112.5 kVA Three-Phase112.5 kVA Oil-Filled Specs →
150 kVA Three-PhaseCurrent Page
225 kVA Three-Phase225 kVA Oil-Filled Specs →

Frequently Asked Questions

How much oil does a 150 kVA oil-filled transformer contain?

A 150 kVA three-phase oil-filled transformer typically contains 80 gallons (303 liters) of Mineral Oil insulating oil.

What are the dimensions of a 150 kVA oil-filled transformer?

Typical dimensions are 55″ H × 41″ W × 32″ D (1400 × 1050 × 810 mm).

How much does a 150 kVA oil-filled transformer weigh?

A 150 kVA oil-filled transformer weighs approximately 1900 lbs (862 kg) including oil.

What is the BIL rating for a 150 kVA transformer?

The standard BIL (Basic Insulation Level) rating is 95 kV, which is standard for 12.47kv-15kv primary.


Related Resources

📊 Complete Reference Charts:

Related Articles


Standards & References

  • IEEE C57.12.00 – General Requirements for Liquid-Immersed Distribution Transformers
  • IEEE C57.12.90 – Test Code for Liquid-Immersed Distribution Transformers
  • IEEE C57.106 – Guide for Acceptance and Maintenance of Insulating Oil
  • NEMA TR-1 – Transformers, Regulators and Reactors
  • EPA 40 CFR 112 – SPCC Requirements

Disclaimer: Specifications shown are typical reference values. Actual specifications vary by manufacturer, voltage class, and application. Oil-filled transformers require proper containment, maintenance, and environmental compliance. Always consult manufacturer datasheets and local codes. Last updated: January 2026