Potential Transformer (PT): Complete Guide to Types, Wiring & Applications

Comprehensive guide to potential transformers for metering and protection in power systems

Technical-schematic-diagram-of-potential-transformer-PT-connection
Potential Transformer (PT) Connection Diagram

A potential transformer (PT) is an instrument transformer used in power systems to step down high
voltages to a safe, standardized level for meters and protective relays. The term “potential transformer” is
commonly used in North America, while “voltage transformer” (VT) is the IEC standard terminology.

This complete guide covers potential transformer construction, working principle, accuracy classes,
wiring configurations, and applications in metering and protection systems.

💡 Key Definition: A potential transformer reduces high primary voltage to a standard secondary
voltage of 120V (ANSI) or 110V (IEC) while maintaining accurate voltage ratio and phase relationship for measuring
instruments.

What is a Potential Transformer?

A potential transformer (also called voltage transformer or VT) is a parallel-connected instrument
transformer that provides an accurate replica of the primary system voltage at a safe, reduced level. PTs are
essential components in:

  • Revenue metering systems
  • Protective relay inputs
  • Synchronizing equipment
  • Power quality monitoring

PT vs VT: What’s the Difference?

TermStandardRegion
Potential Transformer (PT)IEEE/ANSI C57.13North America
Voltage Transformer (VT)IEC 61869-3International

Both terms refer to the same device. For more details on VT types and applications, see our comprehensive voltage
transformer guide
.


Potential Transformer Construction

The construction of a potential transformer includes:

ComponentFunction
Primary WindingHigh voltage side, many turns of fine wire
Secondary WindingLow voltage side (120V or 110V output)
Magnetic CoreSilicon steel laminations for low losses
InsulationOil or resin for HV isolation
TerminalsH1, H2 (primary); X1, X2 (secondary)

Standard Secondary Voltage Ratings

StandardSecondary VoltageApplication
ANSI/IEEE120V, 115V, 69.3VNorth America
IEC110V, 100V, 100/√3VInternational

Working Principle of Potential Transformer

The potential transformer operates on electromagnetic induction:

Voltage Ratio Formula:

Vp/Vs = Np/Ns

Where:

  • Vp = Primary voltage
  • Vs = Secondary voltage (typically 120V)
  • Np = Number of primary winding turns
  • Ns = Number of secondary winding turns
Example: A 4200:120V PT has a ratio of 35:1.
When 4200V is applied to primary, 120V appears at secondary.

Types of Potential Transformers

1. Electromagnetic Potential Transformer

FeatureDescription
Voltage RangeUp to 145kV
Accuracy0.3 to 1.2 class (IEEE)
ConstructionWound type with magnetic core
ApplicationMetering and protection

2. Capacitor Coupled Voltage Transformer (CCVT)

FeatureDescription
Voltage Range69kV to 800kV
ComponentsCapacitor divider + auxiliary transformer
AdvantagesCost-effective at EHV, PLC capability
ApplicationTransmission substations

PT Accuracy Classes (IEEE C57.13)

ClassRatio ErrorApplication
0.3±0.3%Revenue metering
0.6±0.6%Standard metering
1.2±1.2%Indication, protection

PT Burden Classes (IEEE C57.13)

ClassVA RatingPower Factor
W12.5 VA0.10
X25 VA0.70
Y75 VA0.85
Z200 VA0.85

Errors in Potential Transformers

Ratio Error

The difference between ideal and actual voltage ratio:

Ratio Error (%) = [(KnVs – Vp) / Vp] × 100
Where Kn = Rated ratio, Vs = Secondary voltage, Vp = Primary voltage

Phase Angle Error

The angular displacement between primary voltage and reversed secondary voltage. Phase errors affect power and energy
measurements.

Error TypeCauseEffect
Ratio ErrorWinding resistance, core lossesVoltage measurement error
Phase ErrorWinding reactance, magnetizing currentPower factor, energy errors

PT Wiring Configurations

Technical-diagram-showing-two-potential-transformer-PT-wiring-configurations-side-by-side
PT Wiring Configurations: Open Delta vs Wye Connection

Three-Wire Delta Service

Common in medium voltage industrial applications:

  • 2 PTs required (open delta connection)
  • Phase B grounded at secondary
  • Measures line-to-line voltages

Four-Wire Wye Service

Standard for utility metering:

  • 3 PTs required (wye-wye connection)
  • Neutral grounded
  • Measures line-to-neutral voltages

PT vs CT Comparison

FeaturePotential Transformer (PT)Current Transformer (CT)
MeasuresVoltageCurrent
ConnectionParallel (shunt)Series
Standard Output120V or 110V5A or 1A
Open SecondarySafeDangerous
Short SecondaryDangerousSafe

For detailed CT information, see our Current Transformer Complete
Guide
and CT Burden
Calculation Guide
.


🏭 Factory Experience:

  1. Fusing: Always install primary fuses on PT circuits. Use current-limiting fuses rated for
    the system voltage.
  2. Secondary Grounding: Ground X2 terminal for safety. Follow local codes for grounding
    conductor size.
  3. Burden Check: Calculate total connected burden before installation. Include wire resistance
    for long cable runs.
  4. Ferroresonance: When removing one PT from a bank of three, install a loading resistor to
    prevent ferroresonance with cable capacitance.

Frequently Asked Questions

What is a potential transformer used for?

A potential transformer (PT) is used to step down high voltage to a safe level (typically 120V) for
metering, protection relays, and control circuits. It provides electrical isolation between the high voltage system
and measuring instruments.

What is the difference between PT and VT?

There is no technical difference – PT (potential transformer) and VT (voltage transformer) are different names for
the same device. PT is the IEEE/ANSI term used in North America, while VT is the IEC term used internationally.

What is a standard PT ratio?

Common PT ratios include 4200:120 (35:1), 14400:120 (120:1), and 69000:120 (575:1). The ratio depends on the system
voltage, with 120V being the standard secondary voltage in North America.

Can you short circuit a PT secondary?

No, you should never short circuit a PT secondary. Unlike CTs, shorting a PT creates a short circuit on the primary
system, causing extremely high current that can damage or destroy the PT.

What is the accuracy class of a PT?

IEEE C57.13 defines PT accuracy classes as 0.3, 0.6, and 1.2. Class 0.3 PTs are required for revenue metering, while
Class 1.2 is acceptable for indication and protection applications.


Related Articles


References

  1. IEEE C57.13 – Standard Requirements for
    Instrument Transformers
  2. IEC 61869-3 – Instrument Transformers: Inductive
    Voltage Transformers
  3. Flex-Core – Potential Transformers Technical
    Resources

Disclaimer: This information is provided for educational purposes. Always follow applicable standards and
manufacturer guidelines when specifying or installing potential transformers.