112.5 kVA Three-Phase Padmount Transformer: Complete Specifications

Comprehensive specifications for 112.5 kVA dead-front padmount transformer including dimensions, weight, concrete pad requirements, and electrical data

Quick Specifications

Rated Power:112.5 kVAPhase:Three-Phase
Primary Voltage:12470GY/7200Secondary Voltage:208Y/120
Enclosure:Dead-FrontCooling:ONAN
Weight:1800 lbs (816 kg)Concrete Pad:66″ × 66″
Dimensions (H×W×D):38″ × 54″ × 46″ (965 × 1372 × 1168 mm)

A 112.5 kVA padmount transformer is a ground-mounted, oil-filled distribution transformer commonly used in medium commercial, office buildings. This guide provides complete specifications for utility engineers, electrical contractors, and facility planners.

✅ Dead-Front Design: All primary and secondary connections are made inside the locked cabinet, eliminating exposed live parts. This design meets ANSI/IEEE C57.12.28 safety standards for public areas.

112.5 kVA Padmount Transformer Dimensions

112-5-kva-three-phase-padmount-transformer-dimensions
112.5 kVA Three-Phase Padmount Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)965 mm38″
Width (W)1372 mm54″
Depth (D)1168 mm46″
🔧 Installation Note: Unit weight of 1800 lbs allows forklift installation. Concrete pad must be level within 1/4 inch per foot and fully cured (28 days minimum). Maintain minimum 10 feet clearance from buildings per NEC and local fire codes.

Concrete Pad Requirements

The 112.5 kVA padmount transformer requires a properly designed concrete pad for installation:

Pad SpecificationRequirementNotes
Minimum Pad Size66″ × 66″Allow 6″ overhang on all sides
Pad Thickness4-6 inchesReinforced concrete, 3000 PSI minimum
Grade/SlopeLevel ± 1/4″/ftSlight slope away from buildings
Conduit EntryPer utility specsPrimary and secondary duct banks
Curing Time28 days minimumBefore transformer placement

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)1800 lbs (816 kg)Includes all oil and accessories
Oil Volume78 gallons (295 L)Mineral insulating oil
Cooling ClassONANOil Natural, Air Natural
BIL Rating95 kVBasic Insulation Level

Electrical Specifications

ParameterValueNotes
Rated kVA112.5 kVAAt rated voltage and ONAN cooling
Primary Voltage12470GY/7200With taps ±2.5%, ±5%
Secondary Voltage208Y/120Standard service voltage
No-Load Loss250 WCore losses
Load Loss1050 WAt rated load
Total Losses1300 WAt 100% load
Impedance4.0%Per IEEE C57.12.00
Efficiency98.9%DOE 2016 compliant

Secondary Full Load Amps

Full load amperage at secondary voltage for 112.5 kVA three-phase padmount transformer:

Secondary VoltageFull Load AmpsConductor Size
120V541.3 A750+ MCM
208V312.3 A350 MCM
240V270.6 A250 MCM
277V234.5 A250 MCM
480V135.3 A1/0 AWG
Formula:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × √3)
Example at 240V: 270.6 A = (112.5 × 1000) ÷ (240 × 1.732)

When to Choose a 112.5 kVA Padmount Transformer

A 112.5 kVA three-phase padmount transformer is commonly specified for medium commercial facilities, multi-family housing complexes, and retail centers.

Typical Load Distribution for 112.5 kVA Padmount Transformer

Load TypeEstimated Demand
Commercial building HVAC45 kVA
Lighting and receptacles33 kVA
Office equipment22 kVA

Note: Load estimates are typical values. Consult project load study for specific applications.


Related Padmount Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
75.0 kVA Three-Phase75.0 kVA Padmount Specs →
112.5 kVA Three-PhaseCurrent Page
150.0 kVA Three-Phase150.0 kVA Padmount Specs →

Frequently Asked Questions

What size concrete pad do I need for a 112.5 kVA padmount transformer?

A 112.5 kVA padmount transformer requires a minimum pad size of 66″ × 66″ with 4-6 inches thickness of reinforced concrete.

How much does a 112.5 kVA padmount transformer weigh?

A 112.5 kVA padmount transformer weighs approximately 1800 lbs (816 kg) including oil.

What is the difference between dead-front and live-front padmount transformers?

Dead-front designs (like this 112.5 kVA unit) have all connections inside the locked cabinet with no exposed live parts. Live-front designs have bushings exposed on top, requiring additional safety barriers in public areas.


Related Resources

📊 Padmount Reference Charts:

Related Articles


Standards & References


Disclaimer: Specifications shown are typical reference values compliant with IEEE and DOE standards. Actual specifications vary by manufacturer and specific configuration. Always consult manufacturer datasheets and local utility requirements. Last updated: January 2026