1500.0 kVA Three-Phase Padmount Transformer: Complete Specifications

Comprehensive specifications for 1500.0 kVA dead-front padmount transformer including dimensions, weight, concrete pad requirements, and electrical data

Quick Specifications

Rated Power:1500.0 kVAPhase:Three-Phase
Primary Voltage:12470GY/7200Secondary Voltage:480Y/277
Enclosure:Dead-FrontCooling:ONAF
Weight:9600 lbs (4354 kg)Concrete Pad:132″ × 132″
Dimensions (H×W×D):66″ × 98″ × 74″ (1676 × 2489 × 1880 mm)

A 1500.0 kVA padmount transformer is a ground-mounted, oil-filled distribution transformer commonly used in utility distribution, campus substations. This guide provides complete specifications for utility engineers, electrical contractors, and facility planners.

✅ Dead-Front Design: All primary and secondary connections are made inside the locked cabinet, eliminating exposed live parts. This design meets ANSI/IEEE C57.12.28 safety standards for public areas.

1500.0 kVA Padmount Transformer Dimensions

1500-0-kva-three-phase-padmount-transformer-dimensions
1500.0 kVA Three-Phase Padmount Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)1676 mm66″
Width (W)2489 mm98″
Depth (D)1880 mm74″
🔧 Installation Note: Heavy unit (9600 lbs) – requires crane for installation. Concrete pad must be level within 1/4 inch per foot and fully cured (28 days minimum). Maintain minimum 10 feet clearance from buildings per NEC and local fire codes.

Concrete Pad Requirements

The 1500.0 kVA padmount transformer requires a properly designed concrete pad for installation:

Pad SpecificationRequirementNotes
Minimum Pad Size132″ × 132″Allow 6″ overhang on all sides
Pad Thickness4-6 inchesReinforced concrete, 3000 PSI minimum
Grade/SlopeLevel ± 1/4″/ftSlight slope away from buildings
Conduit EntryPer utility specsPrimary and secondary duct banks
Curing Time28 days minimumBefore transformer placement

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)9600 lbs (4354 kg)Includes all oil and accessories
Oil Volume502 gallons (1900 L)Mineral insulating oil
Cooling ClassONAFOil Natural, Air Forced
BIL Rating150 kVBasic Insulation Level

Electrical Specifications

ParameterValueNotes
Rated kVA1500.0 kVAAt rated voltage and ONAF cooling
Primary Voltage12470GY/7200With taps ±2.5%, ±5%
Secondary Voltage480Y/277Standard service voltage
No-Load Loss2100 WCore losses
Load Loss12500 WAt rated load
Total Losses14600 WAt 100% load
Impedance5.75%Per IEEE C57.12.00
Efficiency99.3%DOE 2016 compliant

Secondary Full Load Amps

Full load amperage at secondary voltage for 1500.0 kVA three-phase padmount transformer:

Secondary VoltageFull Load AmpsConductor Size
120V7217.1 A750+ MCM
208V4163.7 A750+ MCM
240V3608.5 A750+ MCM
277V3126.5 A750+ MCM
480V1804.3 A750+ MCM
Formula:
Three-Phase: Amps = (kVA × 1000) ÷ (Voltage × √3)
Example at 240V: 3608.5 A = (1500.0 × 1000) ÷ (240 × 1.732)

When to Choose a 1500.0 kVA Padmount Transformer

This 1500.0 kVA three-phase padmount transformer is designed for major industrial facilities, utility substations, and primary distribution applications.

Typical Load Distribution for 1500.0 kVA Padmount Transformer

Load TypeEstimated Demand
Heavy industrial loads750 kVA
HVAC chillers375 kVA
Auxiliary systems225 kVA

Note: Load estimates are typical values. Consult project load study for specific applications.


Related Padmount Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
1000.0 kVA Three-Phase1000.0 kVA Padmount Specs →
1500.0 kVA Three-PhaseCurrent Page
2000.0 kVA Three-Phase2000.0 kVA Padmount Specs →

Frequently Asked Questions

What size concrete pad do I need for a 1500.0 kVA padmount transformer?

A 1500.0 kVA padmount transformer requires a minimum pad size of 132″ × 132″ with 4-6 inches thickness of reinforced concrete.

How much does a 1500.0 kVA padmount transformer weigh?

A 1500.0 kVA padmount transformer weighs approximately 9600 lbs (4354 kg) including oil.

What is the difference between dead-front and live-front padmount transformers?

Dead-front designs (like this 1500.0 kVA unit) have all connections inside the locked cabinet with no exposed live parts. Live-front designs have bushings exposed on top, requiring additional safety barriers in public areas.


Related Resources

📊 Padmount Reference Charts:

Related Articles


Standards & References


Disclaimer: Specifications shown are typical reference values compliant with IEEE and DOE standards. Actual specifications vary by manufacturer and specific configuration. Always consult manufacturer datasheets and local utility requirements. Last updated: January 2026

Scroll to Top