Transformer Fuse Size Chart: NEC 450.3 Primary & Secondary Sizing [PDF]

 

Transformer Fuse Size Chart

⚡ Quick Answer

For a 100 kVA, 480V–208Y/120V three-phase transformer: Primary current = 120A → Primary
fuse = 150A (at 125%) or 300A (at 250% with secondary protection).
Secondary current = 278A → Secondary fuse = 350A (at 125%). Use Class T time-delay
fuses for 480V applications.

Download: Transformer Fuse Size Chart PDF

2-page A4 reference · NEC 450.3(B) · Single-phase & Three-phase · 25VA-1000 kVA

Download PDF

1. Why Transformer Fuse Sizing Matters

Every distribution
transformer
needs overcurrent protection, and sizing the fuse correctly is one of the most critical
steps in any electrical installation. Size too small, and nuisance tripping during transformer inrush will
cost you downtime. Size too large, and a fault could go undetected until the transformer burns — you’ll know
something went wrong when you smell that distinctive acrid scent of overheated insulation varnish.

When I worked with a contractor on a 480V–120/240V, 75 kVA single-phase bank installation, they had selected
a 400A primary fuse — far too large. The transformer
nameplate
showed a rated primary current of only 156A. Per NEC 450.3(B), the maximum allowed primary
fuse (with no secondary protection) was 200A. The oversized fuse offered almost no protection against a
bolted fault. We could feel the heat radiating from the fuse block even at 60% load — a clear sign it had
never been engineered for the job. We corrected it on the spot.

⚠️ Why All Competitors Publish PDFs
Every top-ranking result for “transformer fuse size chart” is a PDF from Schneider Electric, Eaton, or
Mersen. PDFs are not searchable, not mobile-friendly, and require a download. This article puts all the data
directly in your browser — no PDF needed.

2. NEC 450.3(B) Rules Explained

The National Electrical Code (NEC) Article 450.3(B) governs overcurrent protection for transformers
rated 1000V or less
. The rule differs depending on whether you have primary-only protection or both
primary and secondary protection.

Protection ScenarioPrimary Fuse MaximumSecondary Fuse MaximumWhen to Use
Primary-only (I ≥ 9A)125% of primary FLANot requiredSimple installations; feeder breaker acts as backup
Primary-only (2A ≤ I < 9A)167% of primary FLANot requiredSmall control transformers (100–500VA)
Primary-only (I < 2A)300% of primary FLANot requiredVery small transformers (<25VA at 120V)
Primary + Secondary (I ≥ 9A)250% of primary FLA125% of secondary FLARecommended for 15 kVA and larger
Primary + Secondary (<9A sec)250% of primary FLA167% of secondary FLASmall control transformers with protected output
📌 Key Note on Standard Fuse Sizes
If the calculated fuse size does not match a standard rating, NEC 450.3 allows you to round
up to the next standard size. Standard fuse ratings follow the sequence: 15, 20, 25, 30,
35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500A.

3. Fuse Calculation Formula & Quick Steps

Single-Phase Primary Current (A):
I_primary = kVA × 1000 ÷ V_primary
Example: 25 kVA, 480V → 25,000 ÷ 480 = 52.1A
Three-Phase Primary Current (A):
I_primary = kVA × 1000 ÷ (V_primary × 1.732)
Example: 100 kVA, 480V → 100,000 ÷ (480 × 1.732) = 120.3A
  1. Read the transformer nameplate — confirm
    kVA, primary voltage, and secondary voltage.
  2. Calculate rated primary current using the formula above.
  3. Decide: primary-only protection (125%) or both primary + secondary (250%/125%).
  4. Multiply primary FLA by the allowed percentage to get maximum fuse size.
  5. Round up to the next standard fuse size from NEMA ST 20 list.
  6. Calculate secondary FLA and apply 125% if secondary protection is required.
  7. Select fuse class: Class CC for ≤30A, Class T or RK5 for >30A at 480V/600V.

📥 Download: Free Printable Fuse Size Chart (PDF)
Need this chart on the job site? Download the Transformer Fuse Size Chart PDF (2 pages) — includes all NEC 450.3 tables for single-phase, three-phase, and control transformers. Print it, laminate it, keep it in your toolbox.
 

4. Single-Phase Transformer Fuse Size Chart

The tables below cover the most common single-phase distribution transformer ratings. Primary fuse values are
given at 125% (primary-only) and 250% (with secondary protection). All
values are rounded up to the next standard fuse size per NEC 450.3(B).

4a. Primary at 480V, Secondary at 120/240V (Most Common)

kVAPrimary FLA (480V)Primary Fuse 125%Primary Fuse 250%Secondary FLA (240V)Secondary Fuse 125%
5 kVA10.4A15A30A20.8A25A
10 kVA20.8A25A60A41.7A50A
15 kVA31.3A40A80A62.5A80A
25 kVA52.1A70A150A104.2A125A
37.5 kVA78.1A100A200A156.3A200A
50 kVA104.2A125A250A208.3A250A
75 kVA156.3A200A400A312.5A400A
100 kVA208.3A250A500A416.7A500A
167 kVA347.9A450A800A†695.8A800A†
250 kVA520.8A600A†1200A†1041.7A1200A†

† Values above 600A require current-limiting fuses or
high-interrupting-capacity circuit breakers. Consult AHJ.

4b. Primary at 240V, Secondary at 120V

kVAPrimary FLA (240V)Primary Fuse 125%Primary Fuse 250%Secondary FLA (120V)Secondary Fuse 125%
5 kVA20.8A25A60A41.7A50A
10 kVA41.7A50A110A83.3A100A
15 kVA62.5A80A175A125.0A150A
25 kVA104.2A125A300A208.3A250A
50 kVA208.3A250A500A416.7A500A
75 kVA312.5A400A800A†625.0A800A†

5. Three-Phase Transformer Fuse Size Chart

Three-phase transformer fuse sizing uses the same NEC 450.3(B) multipliers, but primary/secondary currents
are divided by √3 (1.732). These tables cover the most popular configurations used in commercial
and industrial distribution
.

5a. Primary 480V, Secondary 208Y/120V (Most Common Commercial)

kVAPrimary FLA (480V)Primary Fuse 125%Primary Fuse 250%Secondary FLA (208V)Secondary Fuse 125%
15 kVA18.0A25A45A41.6A50A
30 kVA36.1A45A90A83.3A100A
45 kVA54.1A70A150A124.9A150A
75 kVA90.2A110A225A208.2A250A
112.5 kVA135.3A175A350A312.4A400A
150 kVA180.4A225A450A416.4A500A
225 kVA270.6A350A700A624.6A800A†
300 kVA360.8A450A900A†832.7A1000A†
500 kVA601.4A700A†1500A†1387.8A1600A†
750 kVA902.1A1100A†2250A†2081.7A2500A†
1000 kVA1202.8A1500A†3000A†2775.7A3500A†

† Above 600A: use low-voltage power circuit breakers or
current-limiting fuse assemblies. Check local AHJ requirements.

5b. Primary 600V, Secondary 208Y/120V (Industrial)

kVAPrimary FLA (600V)Primary Fuse 125%Primary Fuse 250%Secondary FLA (208V)Secondary Fuse 125%
15 kVA14.4A20A35A41.6A50A
30 kVA28.9A35A70A83.3A100A
75 kVA72.2A90A175A208.2A250A
150 kVA144.3A175A350A416.4A500A
300 kVA288.7A350A700A832.7A1000A†
500 kVA481.1A600A†1200A†1387.8A1600A†

6. Control Transformer Fuse Chart (25VA–1000VA)

Control transformers (used in machine tool circuits, PLC panels, HVAC controls) operate at much lower VA
ratings. NEMA ST 20 and Schneider Electric’s 9070 series define specific fuse recommendations. These
typically use Class CC time-delay rejection-style fuses (1-1/2″ × 13/32″).

VA RatingPrimary VoltagePrimary FLAPrimary Fuse (NEC)Secondary (120V) FLASecondary Fuse (NEC)Fuse Class
25 VA480V0.052A1/4A (300%)0.21A1/4AClass CC
50 VA480V0.10A1/4A (300%)0.42A1AClass CC
100 VA480V0.21A1/2A (167–300%)0.83A1AClass CC
150 VA480V0.31A1A (167–300%)1.25A2AClass CC
250 VA480V0.52A1A (167%)2.08A3AClass CC
500 VA480V1.04A2A (167%)4.17A6AClass CC
750 VA480V1.56A2A (125%)6.25A8AClass CC
1000 VA480V2.08A3A (125%)8.33A10AClass CC
500 VA120V4.17A6A (125%)4.17A6AClass CC
1000 VA120V8.33A10A (125%)8.33A10AClass CC
✅ Factory Note on Control Transformers
For control transformers with primary currents below 2A (very common at 480V primary, <1 kVA), NEC allows
up to 300% primary fuse sizing. However, in our factory, we always recommend using the smallest available
standard fuse that won’t cause nuisance tripping during inrush — typically 2–3× the rated primary current
for time-delay fuses. When a control transformer on a machine tool panel blows its 1A Class CC fuse
repeatedly, nine times out of ten it’s because someone replaced a time-delay fuse with a fast-blow type. The
tell-tale sign: the fuse looks physically intact but measures open — fast-blow fuses can fail cleanly at
impulse currents without visible damage.

7. Class CC vs Class T: Which Fuse to Choose?

Transformer Fuse Type Comparison

🔵 Class CC — Time Delay (for Control Transformers)

  • Size: 1-1/2″ × 13/32″ (midget)
  • Rating: 1/4A to 30A, 600V
  • Type: Time-delay, rejection-style
  • AIC: 100,000A (UL Listed)
  • Use: Control Xfmrs ≤1 kVA at 480V
  • Examples: Littelfuse CCMR, Bussmann FNQ-R

🟢 Class T — Fast-Acting (for Distribution Transformers)

  • Size: 1-1/16″ (compact), 200kA AIC
  • Rating: 1A to 1200A, 300V or 600V
  • Type: Fast-acting, current-limiting
  • AIC: 200,000A (superior protection)
  • Use: Distribution Xfmrs 15 kVA–1000 kVA
  • Examples: Bussmann JJN/JJS, Littelfuse JLLN
FeatureClass CCClass TClass RK5Class L
Max Rating30A1200A600A6000A
Voltage600V300V/600V250V/600V600V
AIC (kA)100200200200
Time-Delay?YesSomeYesSome
Best UseControl XfmrsDistributionDistributionLarge Power
Typical kVA Range<1 kVA15–500 kVA15–1000 kVA500+ kVA
Physical InterlockRejection clipCompactStandardBolted

8. Factory Tips: 5 Common Fuse Sizing Mistakes

🚫 Mistake 1: Using the Circuit Breaker Rating as the Fuse Size
A 100A feeder breaker does NOT mean you need a 100A primary fuse. The fuse protects the transformer, not the
feeder. Calculate from the transformer’s own rated primary current — which might be only 36A for a 30 kVA,
480V transformer. Installing a 100A fuse here provides effectively no transformer protection.
🚫 Mistake 2: Forgetting the Inrush Factor
Transformers draw 6–12× rated current for 100ms during energization. Always use time-delay
fuses
for transformer primary protection. A fast-acting fuse sized at 125% will blow on every
switching. The time-delay characteristic allows inrush to pass while still interrupting sustained fault
current.
🚫 Mistake 3: Applying 250% Without Secondary Protection
NEC 450.3(B) only allows 250% on the primary fuse when separate secondary overcurrent
protection
is installed. Without it, the maximum is 125%. I’ve seen inspections fail because
contractors assumed 250% was always allowed — it isn’t.
🚫 Mistake 4: Ignoring the kVA-to-kW Difference
When sizing a transformer, customers often use load kW to select kVA. A 100 kW load at 0.8 power factor
requires a 125
kVA transformer
— not 100 kVA. Undersizing the transformer means the primary fuse may nuisance-trip
during peak demand.
💡 Mistake 5: Using kVA Fuse Tables from Different Voltages
A fuse size table for a 480V primary transformer is completely different from one at 208V or 240V. Primary
FLA at 208V is 2.3× higher than at 480V for the same kVA. Always verify the actual primary
voltage
on the nameplate before selecting fuse size.
 

📄 Take This Chart With You
All the tables on this page in a printer-friendly 2-page format: Download Transformer Fuse Size Chart PDF (NEC 450.3). Perfect for field engineers and electricians.
 

9. Frequently Asked Questions

What size fuse for a 25 kVA 480V transformer?
Primary FLA = 25,000 ÷ 480 = 52.1A. With primary-only protection: fuse = 52.1 × 1.25 =
65.1A → round up to 70A. With both primary and secondary protection: primary fuse =
52.1 × 2.5 = 130.3A → round up to 150A. Use a time-delay Class T or RK5 fuse.
What is the NEC rule for transformer fuse sizing?
NEC 450.3(B): Primary-only: fuse ≤ 125% of rated primary current (if ≥9A), ≤167% (if
2–9A), ≤300% (if <2A). With primary + secondary protection: primary fuse ≤ 250%, secondary fuse ≤
125% of secondary rated current. Always round up to the next standard fuse size.
What type of fuse for a 480V distribution transformer?
For 15 kVA–1000 kVA transformers at 480V: use Class T current-limiting,
time-delay fuses
(Bussmann JJN or equivalent). For 480V control transformers below 30A: use
Class CC rejection-style time-delay fuses (Bussmann FNQ-R or Littelfuse CCMR). Both
types provide 100–200kA AIC interrupting capacity required at 480V.
Can I use a circuit breaker instead of a fuse?
Yes — NEC 450.3 applies equally to fuses and circuit breakers. The 125%/250% multipliers
are the same. However, fuses are generally preferred for transformer primary protection because they
clear fault currents faster and have higher AIC ratings, reducing through-fault damage to the transformer
windings
.
What fuse for a 100 kVA three-phase 480V to 208V transformer?
Primary FLA = 100,000 ÷ (480 × 1.732) = 120.3A. Primary fuse at 125% = 150A. With
secondary protection, primary fuse at 250% = 300A. Secondary FLA at 208V = 100,000 ÷ (208 × 1.732) =
277.5A. Secondary fuse at 125% = 350A. This is among the most common configurations in US commercial
buildings.
Do I need secondary fuse protection on a distribution transformer?
NEC does not mandate secondary protection for all transformers — primary-only protection
at 125% is code-compliant. However, secondary protection provides better fault isolation and allows a
larger (250%) primary fuse that avoids nuisance tripping. For transformers above 112.5 kVA, secondary
protection is strongly recommended. Consult the AHJ and your transformer
protection
engineer.

Related Resources

Standards Referenced:
NEC 2023 Article
450.3(B)
|
NEMA ST 20 —
Transformers, Dry-Type
|
UL 248 —
Low-Voltage Fuses

Scroll to Top