50.0 kVA Single-Phase Padmount Transformer: Complete Specifications

Comprehensive specifications for 50.0 kVA dead-front padmount transformer including dimensions, weight, concrete pad requirements, and electrical data

Quick Specifications

Rated Power:50.0 kVAPhase:Single-Phase
Primary Voltage:12470GY/7200Secondary Voltage:120/240
Enclosure:Dead-FrontCooling:ONAN
Weight:900 lbs (408 kg)Concrete Pad:52″ × 52″
Dimensions (H×W×D):28″ × 36″ × 37″ (711 × 914 × 927 mm)

A 50.0 kVA padmount transformer is a ground-mounted, oil-filled distribution transformer commonly used in multi-family housing, retail centers. This guide provides complete specifications for utility engineers, electrical contractors, and facility planners.

✅ Dead-Front Design: All primary and secondary connections are made inside the locked cabinet, eliminating exposed live parts. This design meets ANSI/IEEE C57.12.28 safety standards for public areas.

50.0 kVA Padmount Transformer Dimensions

50-0-kva-single-phase-padmount-transformer-dimensions
50.0 kVA Single-Phase Padmount Transformer Dimensions (Typical)
DimensionMetric (mm)Imperial (inches)
Height (H)711 mm28″
Width (W)914 mm36″
Depth (D)927 mm37″
🔧 Installation Note: Unit weight of 900 lbs allows forklift installation. Concrete pad must be level within 1/4 inch per foot and fully cured (28 days minimum). Maintain minimum 10 feet clearance from buildings per NEC and local fire codes.

Concrete Pad Requirements

The 50.0 kVA padmount transformer requires a properly designed concrete pad for installation:

Pad SpecificationRequirementNotes
Minimum Pad Size52″ × 52″Allow 6″ overhang on all sides
Pad Thickness4-6 inchesReinforced concrete, 3000 PSI minimum
Grade/SlopeLevel ± 1/4″/ftSlight slope away from buildings
Conduit EntryPer utility specsPrimary and secondary duct banks
Curing Time28 days minimumBefore transformer placement

Weight and Oil Specifications

SpecificationValueNotes
Total Weight (with oil)900 lbs (408 kg)Includes all oil and accessories
Oil Volume44 gallons (167 L)Mineral insulating oil
Cooling ClassONANOil Natural, Air Natural
BIL Rating95 kVBasic Insulation Level

Electrical Specifications

ParameterValueNotes
Rated kVA50.0 kVAAt rated voltage and ONAN cooling
Primary Voltage12470GY/7200With taps ±2.5%, ±5%
Secondary Voltage120/240Standard service voltage
No-Load Loss105 WCore losses
Load Loss480 WAt rated load
Total Losses585 WAt 100% load
Impedance2.0%Per IEEE C57.12.00
Efficiency98.9%DOE 2016 compliant

Secondary Full Load Amps

Full load amperage at secondary voltage for 50.0 kVA single-phase padmount transformer:

Secondary VoltageFull Load AmpsConductor Size
120V416.7 A750+ MCM
208V240.4 A250 MCM
240V208.3 A4/0 AWG
277V180.5 A3/0 AWG
480V104.2 A#2 AWG
Formula:
Single-Phase: Amps = (kVA × 1000) ÷ Voltage
Example at 240V: 208.3 A = (50.0 × 1000) ÷ 240

When to Choose a 50.0 kVA Padmount Transformer

The 50.0 kVA single-phase padmount transformer is ideal for residential subdivisions (serving 10-20 homes) and small commercial buildings under 5,000 sq ft.

Typical Load Distribution for 50.0 kVA Padmount Transformer

Load TypeEstimated Demand
Residential homes (3-8 homes)25 kVA
Street lighting5 kVA
Small retail15 kVA

Note: Load estimates are typical values. Consult project load study for specific applications.


Related Padmount Transformer Sizes

Compare with adjacent kVA ratings:

kVA RatingLink
37.5 kVA Single-Phase37.5 kVA Padmount Specs →
50.0 kVA Single-PhaseCurrent Page
75.0 kVA Single-Phase75.0 kVA Padmount Specs →

Frequently Asked Questions

What size concrete pad do I need for a 50.0 kVA padmount transformer?

A 50.0 kVA padmount transformer requires a minimum pad size of 52″ × 52″ with 4-6 inches thickness of reinforced concrete.

How much does a 50.0 kVA padmount transformer weigh?

A 50.0 kVA padmount transformer weighs approximately 900 lbs (408 kg) including oil.

What is the difference between dead-front and live-front padmount transformers?

Dead-front designs (like this 50.0 kVA unit) have all connections inside the locked cabinet with no exposed live parts. Live-front designs have bushings exposed on top, requiring additional safety barriers in public areas.


Related Resources

📊 Padmount Reference Charts:

Related Articles


Standards & References


Disclaimer: Specifications shown are typical reference values compliant with IEEE and DOE standards. Actual specifications vary by manufacturer and specific configuration. Always consult manufacturer datasheets and local utility requirements. Last updated: January 2026

Scroll to Top