Comprehensive full load amperage chart for oil-immersed distribution transformers. Find FLA values for all
standard kVA ratings at common voltages, plus wire sizing recommendations.
⚡ FLA Calculation Formulas
Single-Phase:FLA = (kVA × 1000) ÷ Voltage | Three-Phase:FLA = (kVA × 1000) ÷ (Voltage × √3) |
Knowing the Full Load Amperage (FLA) of your oil-filled transformer is essential for proper
conductor sizing, fuse selection, and protection coordination. This chart provides FLA values at
all common secondary voltages including 600V for Canadian applications.
Single-Phase Oil-Filled Transformer FLA Chart
Full load amperage for single-phase oil-filled transformers at common secondary voltages:
| kVA | Full Load Amps (FLA) by Secondary Voltage | Specs | |||||
|---|---|---|---|---|---|---|---|
| 120V | 208V | 240V | 277V | 480V | 600V | ||
| 10 kVA | 83.3 A | 48.1 A | 41.7 A | 36.1 A | 20.8 A | 16.7 A | View → |
| 15 kVA | 125.0 A | 72.1 A | 62.5 A | 54.2 A | 31.2 A | 25.0 A | View → |
| 25 kVA | 208.3 A | 120.2 A | 104.2 A | 90.3 A | 52.1 A | 41.7 A | View → |
| 37.5 kVA | 312.5 A | 180.3 A | 156.2 A | 135.4 A | 78.1 A | 62.5 A | View → |
| 50 kVA | 416.7 A | 240.4 A | 208.3 A | 180.5 A | 104.2 A | 83.3 A | View → |
| 75 kVA | 625.0 A | 360.6 A | 312.5 A | 270.8 A | 156.2 A | 125.0 A | View → |
| 100 kVA | 833.3 A | 480.8 A | 416.7 A | 361.0 A | 208.3 A | 166.7 A | View → |
| 167 kVA | 1391.7 A | 803.0 A | 695.8 A | 602.9 A | 347.9 A | 278.3 A | View → |
| 250 kVA | 2083.3 A | 1201.9 A | 1041.7 A | 902.5 A | 520.8 A | 416.7 A | View → |
| 333 kVA | 2775.0 A | 1600.9 A | 1387.5 A | 1202.2 A | 693.8 A | 555.0 A | View → |
| 500 kVA | 4166.7 A | 2403.8 A | 2083.3 A | 1805.1 A | 1041.7 A | 833.3 A | View → |
Three-Phase Oil-Filled Transformer FLA Chart
Full load amperage for three-phase oil-filled transformers. Note: Three-phase FLA is calculated
using the √3 (1.732) factor.
| kVA | Full Load Amps (FLA) by Secondary Voltage | Specs | ||||
|---|---|---|---|---|---|---|
| 208V | 240V | 277V | 480V | 600V | ||
| 15 kVA | 41.6 A | 36.1 A | 31.3 A | 18.0 A | 14.4 A | View → |
| 30 kVA | 83.3 A | 72.2 A | 62.6 A | 36.1 A | 28.9 A | View → |
| 45 kVA | 124.9 A | 108.3 A | 93.8 A | 54.1 A | 43.3 A | View → |
| 75 kVA | 208.2 A | 180.4 A | 156.4 A | 90.2 A | 72.2 A | View → |
| 112.5 kVA | 312.3 A | 270.6 A | 234.6 A | 135.3 A | 108.2 A | View → |
| 150 kVA | 416.4 A | 360.8 A | 312.8 A | 180.4 A | 144.3 A | View → |
| 225 kVA | 624.6 A | 541.3 A | 469.2 A | 270.6 A | 216.5 A | View → |
| 300 kVA | 832.8 A | 721.7 A | 625.6 A | 360.8 A | 288.7 A | View → |
| 500 kVA | 1388.0 A | 1202.8 A | 1042.6 A | 601.4 A | 481.1 A | View → |
| 750 kVA | 2082.0 A | 1804.2 A | 1564.2 A | 902.1 A | 721.7 A | View → |
| 1000 kVA | 2776.0 A | 2405.6 A | 2085.5 A | 1202.8 A | 962.3 A | View → |
| 1500 kVA | 4164.0 A | 3608.4 A | 3128.3 A | 1804.2 A | 1443.4 A | View → |
| 2000 kVA | 5552.0 A | 4811.3 A | 4171.1 A | 2405.6 A | 1924.5 A | View → |
| 2500 kVA | 6940.0 A | 6014.1 A | 5213.9 A | 3007.0 A | 2405.6 A | View → |
Conductor Sizing Guide for Oil-Filled Transformers
Proper conductor sizing is critical for safety and code compliance. Use this guide based on copper conductors with
75°C insulation per NEC Table 310.16.
| Current Range | Copper Conductor | Typical Application |
|---|---|---|
| 0-20 A | #12 AWG | Small branch circuits |
| 21-30 A | #10 AWG | Standard branch circuits |
| 31-50 A | #8 – #6 AWG | Sub-panels, small equipment |
| 51-100 A | #4 – #1 AWG | Service entrance, panels |
| 101-150 A | 1/0 – 2/0 AWG | Main service, feeders |
| 151-200 A | 3/0 – 4/0 AWG | Large feeders |
| 201-300 A | 250-350 MCM | Commercial service |
| 301-500 A | 400-750 MCM | Industrial feeders |
| 500+ A | Parallel conductors | Large industrial, substations |
cable terminations. Use appropriate weatherhead and bushings for outdoor installations.
FLA Calculation Examples
Example 1: Single-Phase 75 kVA at 240V
FLA = (75 × 1000) ÷ 240 = 312.5 AmpsRecommended conductor: 350 MCM copper
Example 2: Three-Phase 500 kVA at 480V
FLA = (500 × 1000) ÷ (480 × 1.732) = 601.4 AmpsRecommended conductor: Parallel 350 MCM copper
Example 3: Three-Phase 1000 kVA at 600V (Canadian)
FLA = (1000 × 1000) ÷ (600 × 1.732) = 962.3 AmpsRecommended: Parallel 500 MCM copper
Frequently Asked Questions
What is Full Load Amps (FLA)?
FLA is the current drawn by a transformer when it is delivering its rated kVA at its rated secondary voltage. It
represents the maximum continuous current the secondary conductors must carry.
Can oil-filled transformers handle overloads?
Yes, oil-filled transformers have excellent overload capability due to the thermal mass of the oil. Per IEEE C57.91,
they can typically handle 150% load for 30 minutes or 120% for 2 hours without
damage.
Why include 600V in the chart?
600V is the standard commercial/industrial voltage in Canada. Many oil-filled transformers are
specified with 600V secondary for Canadian applications.
Related Resources
📊 More Reference Charts:
- Oil-Filled
Sizing Chart – Complete kVA selection guide - Transformer
Oil Complete Guide – Types, testing, maintenance
Standards & References
- NEC Article 450 – Transformer Protection Requirements
- IEEE C57.91 – Loading
Guide for Mineral-Oil-Immersed Transformers - IEEE C57.12.00 –
General Requirements for Liquid-Immersed Transformers
Disclaimer: FLA values are calculated at nameplate voltage. Actual current may vary based on voltage regulation
and load power factor. Wire sizing recommendations are guidelines only – always follow NEC/CEC requirements and
consult with a licensed electrical engineer. Last updated: January 2026