Comprehensive full load amperage chart for dead-front padmount transformers. Find FLA values for all standard kVA
ratings at common voltages, plus wire sizing recommendations.
⚡ FLA Calculation Formulas
Single-Phase:FLA = (kVA × 1000) ÷ Voltage | Three-Phase:FLA = (kVA × 1000) ÷ (Voltage × √3) |
Knowing the Full Load Amperage (FLA) of your padmount transformer is essential for proper
conductor sizing, circuit breaker selection, and protection coordination. This chart provides FLA
values at all common secondary voltages.
Single-Phase Padmount Transformer FLA Chart
Full load amperage for single-phase padmount transformers at common secondary voltages:
| kVA | Full Load Amps (FLA) by Secondary Voltage | Specs | ||||
|---|---|---|---|---|---|---|
| 120V | 208V | 240V | 277V | 480V | ||
| 25 kVA | 208.3 A | 120.2 A | 104.2 A | 90.3 A | 52.1 A | View → |
| 37.5 kVA | 312.5 A | 180.3 A | 156.3 A | 135.4 A | 78.1 A | View → |
| 50 kVA | 416.7 A | 240.4 A | 208.3 A | 180.5 A | 104.2 A | View → |
| 75 kVA | 625.0 A | 360.6 A | 312.5 A | 270.8 A | 156.3 A | View → |
| 100 kVA | 833.3 A | 480.8 A | 416.7 A | 361.0 A | 208.3 A | View → |
| 167 kVA | 1391.7 A | 803.0 A | 695.8 A | 602.9 A | 347.9 A | View → |
Three-Phase Padmount Transformer FLA Chart
Full load amperage for three-phase padmount transformers. Note: Three-phase FLA is calculated using
the √3 (1.732) factor.
| kVA | Full Load Amps (FLA) by Secondary Voltage | Specs | |||
|---|---|---|---|---|---|
| 208V | 240V | 277V | 480V | ||
| 75 kVA | 208.2 A | 180.4 A | 156.4 A | 90.2 A | View → |
| 112.5 kVA | 312.3 A | 270.6 A | 234.6 A | 135.3 A | View → |
| 150 kVA | 416.4 A | 360.8 A | 312.8 A | 180.4 A | View → |
| 225 kVA | 624.6 A | 541.3 A | 469.2 A | 270.6 A | View → |
| 300 kVA | 832.8 A | 721.7 A | 625.6 A | 360.8 A | View → |
| 500 kVA | 1388.0 A | 1202.8 A | 1042.6 A | 601.4 A | View → |
| 750 kVA | 2082.0 A | 1804.2 A | 1564.0 A | 902.1 A | View → |
| 1000 kVA | 2776.0 A | 2405.6 A | 2085.3 A | 1202.8 A | View → |
| 1500 kVA | 4164.0 A | 3608.4 A | 3128.0 A | 1804.2 A | View → |
| 2000 kVA | 5552.0 A | 4811.3 A | 4171.0 A | 2405.6 A | View → |
| 2500 kVA | 6940.0 A | 6014.1 A | 5213.8 A | 3007.0 A | View → |
Conductor Sizing Guide for Padmount Transformers
Proper conductor sizing is critical for safety and code compliance. Use this guide based on copper conductors with
75°C insulation per NEC Table 310.16.
| Current Range | Copper Conductor | Typical Application |
|---|---|---|
| 0-20 A | #12 AWG | Small branch circuits |
| 21-30 A | #10 AWG | Standard branch circuits |
| 31-50 A | #8 – #6 AWG | Sub-panels, small equipment |
| 51-100 A | #4 – #1 AWG | Service entrance, panels |
| 101-150 A | 1/0 – 2/0 AWG | Main service, feeders |
| 151-200 A | 3/0 – 4/0 AWG | Large feeders |
| 201-300 A | 250-350 MCM | Commercial service |
| 301-500 A | 400-750 MCM | Industrial feeders |
| 500+ A | Parallel conductors | Large industrial loads |
continuous loads. Consult a licensed electrician for final sizing.
FLA Calculation Examples
Example 1: Single-Phase 50 kVA at 240V
FLA = (50 × 1000) ÷ 240 = 208.3 AmpsRecommended conductor: 4/0 AWG copper
Example 2: Three-Phase 300 kVA at 480V
FLA = (300 × 1000) ÷ (480 × 1.732) = 360.8 AmpsRecommended conductor: 500 MCM copper
Example 3: Three-Phase 1000 kVA at 208V
FLA = (1000 × 1000) ÷ (208 × 1.732) = 2776 AmpsRecommended: Multiple parallel 750 MCM conductors
Frequently Asked Questions
What is Full Load Amps (FLA)?
FLA is the current drawn by a transformer when it is delivering its rated kVA at its rated secondary voltage. It
represents the maximum continuous current the secondary conductors must carry.
How do I calculate FLA for a padmount transformer?
For single-phase: FLA = kVA × 1000 ÷ Voltage. For three-phase: FLA = kVA × 1000 ÷
(Voltage × 1.732).
What size breaker do I need?
The primary overcurrent protection is typically set at 125% of transformer FLA per NEC Article 450.
Secondary protection depends on impedance and load characteristics.
Related Resources
📊 More Reference Charts:
- Padmount
Sizing Chart – Complete kVA selection guide - Pad
Mounted Transformer Complete Guide – Types, components, installation
Standards & References
- NEC Article 450 – Transformer Protection Requirements
- NEC Table 310.16 – Allowable Ampacities for Conductors
- IEEE C57.12.00 –
General Requirements for Distribution Transformers
Disclaimer: FLA values are calculated at nameplate voltage. Actual current may vary based on voltage regulation
and load power factor. Wire sizing recommendations are guidelines only – always follow NEC requirements and
consult with a licensed electrical engineer. Last updated: January 2026